-6%

CMP-2000 Digital clamp-on multimeter

Availability:

5 in stock


It provides:

  • AC current measurement (TRUE RMS) up to 1500 A and DC up to 2000 A.
  • Measurement of INRUSH current in start-up phase of electrical device.
  • AC voltage measurement (TRUE RMS) up to 750 V and DC up to 1000 V.
  • Resistance measurement and continuity test:
    – continuity test with acoustic signalling (beeper) for resistance below 30 Ω.
  • Capacitance measurement.
  • Temperature measurement (Fahrenheit or Celsius).
  • Frequency measurement.
  • Duty cycle measurement.
  • Diode test.

61,859 65,809

5 in stock

Compare
  • Universal clamp meter, enabling the maintenance of current measurements up to 2000 A, with the diameter of the clamp as 57 mm, and bus bar to 70 * 18 mm
    The instrument has an electronic overload protection of all functions and ranges.

Category:
Weight 0.6 kg
Dimensions 28 × 11 × 5 cm

AC current measurement (TRUE RMS) up to 1500 A and DC up to 2000 A.

Measurement of INRUSH current in start-up phase of electrical device.

AC voltage measurement (TRUE RMS) up to 750 V and DC up to 1000 V.

Resistance measurement and continuity test:

  • continuity test with acoustic signalling (beeper) for resistance below 30 Ω.

Capacitance measurement

Temperature measurement (Fahrenheit or Celsius).

Frequency measurement.

Duty cycle measurement.

Diode test.

Additionally:

  • safe, insulated measuring clamp,
  • autoranging,
  • „DATA HOLD” function, for holding measured values,
  • backlit LCD,
  • „DC ZERO” mode of measurement for DC current, possibility to zero the display and reading relative actual value less stored „zero” value,
  • „MAX/MIN” function,
  • over range indication,
  • „AUTO-OFF” function after 30 min.

Electric security:

  • measurement category: CAT IV 600 V acc. to EN 61010 – 1,
  • protection class acc. to EN 60529: IP20,

Other technical data:

  • power supply, 9 V battery type 6LR61,
  • display: 6600 counts, backlit LCD,
  • continuity test: threshold 30 Ω,
  • diode test: test current of 0,8 mA , typical open circuit voltage 3,2 V DC, typical,
  • low battery indication: BAT displayed,
  • over range indication: ‘OL’ displayed,
  • temperature sensor: type K thermocouple,
  • input impedance: ca.10 MΩ (V DC and V AC),
  • AC bandwidth: 50…500 Hz,
  • auto power OFF: 30 minutes,
  • dimensions: 281 x 108 x 53 mm,
  • weight: 570 g (with battery),
  • accordance with following standards: EN 61010 – 1, EN 61010 – 2-032.

Rated operational conditions:

  • able to open the clamp: Ø 57 mm wire 70 x 18 mm bus bar,
  • operating temperature: 0…+50 °C,
  • storage temperature: -20…+60 °C,
  • operating altitude: max 2000 m.

 

DC current measurement

Range Resolution Accuracy
0,0…659,9 A 0,1 A ±(2,0% m.v. + 5 digits)
660…2000 A 1 A ±(3,0% m.v. + 5 digits) for 660…1000 A
±(5,0% m.v. + 5 digits) for 1000…2000 A

AC current measurement (TRUE RMS)

Range Resolution Accuracy
0,0…659,9 A 0,1 A ±(2,0% m.v. + 10 digits) for 50…60 Hz
±(3,0% m.v. + 10 digits) for 61…400 Hz
660…1500 A 1 A ±(2,5% m.v. + 10 digits) for 50…60 Hz
i 660…1000 A
±(3,5% m.v. + 10 digits) for 61…400 Hz
and 660…1000 A
±(5,0% m.v. + 10 digits) for 50…400 Hz
and 1000…1500

DC voltage measurement

Range Resolution Accuracy
0,000…6,599 V 0,001 V ±(0,5% m.v. + 2 digits)
6,60…65,99 V 0,01 V
66,0…659,9 V 0,1 V
660…1000 V 1 V

AC voltage measurement (true RMS)

 

Range Resolution Accuracy
0,000…6,599 V 0,001 V ±(1,5% m.v. + 8 digits)
for 50…500 Hz
6,60…65,99 V 0,01 V
66,0…659,9 V 0,1 V
660…750 V 1

Resistance measurement

Range Resolution Accuracy
0,0…659,9 Ω 0,1 Ω ±(1,0% m.v. + 5 digits)
0,660…6,599 kΩ 0,001 kΩ
6,60…65,99 kΩ 0,01 kΩ
66,0…659,9 kΩ 0,1 kΩ
0,660…6,599 MΩ 0,001 MΩ ±(2,0% m.v. + 5 digits)
6,60…66,00 MΩ 0,01 MΩ ±(3,5% m.v. + 5 digits)

Capacitance measurement

Range Resolution Accuracy
0,0…6,599 nF 0,001 nF ±(3,0% m.v. + 30 digits)
6,60…65,99 nF 0,01 nF ±(3,0% m.v. + 10 digits)
66,0…559,9 nF 0,1 nF ±(3,0% m.v. + 30 digits)
6,600…59,999 µF 0,001 µF ±(3,0% m.v. + 10 digits)
66,00…659,99 µF 0,01 µF
660…659,999 µF 0,100 µF
0,660…6,600 mF 0,001 mF

Frequency measurement

Range Resolution Accuracy
10…65,99 Hz 0,01 Hz ±(0,1% m.v. + 5 digits)
66,0…659,9 Hz 0,1 Hz
0,660…6,599 kHz 0,001 kHz
6,60…65,99 kHz 0,01 kHz
66,0…659,9 kHz 0,1 kHz
0,660…1,000 MHz 0,001 MHz

Temperature measurement

Range Resolution Accuracy
-20…0°C 1°C ±(2,0% m.v. + 3°C)
0…399°C ±(1,0% m.v. + 2°C)
400…1000°C ±(2,0% m.v. + 3°C)
-4…31°F 1°F ±(2,0% m.v. + 6°F)
32..749°F ±(1,0% m.v. + 4°F)
750…1832°F ±(2,0% m.v. + 6°F)

 

Duty cycle measurement

 

ange Resolution Accuracy
5…95% 0,1% ±(2,0% m.v. + 10 digits)

„m.v.”- measured value

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “CMP-2000 Digital clamp-on multimeter”

There are no reviews yet.

  • Plam Size Digital Multimeters UT132B

    0 out of 5
    (0)

    UT132 Series is a 3.5 digit palm sized digital multimeter with stable performance, and fashionable design. UT132 are safe and reliable manual ranged multimeters that can be used for measuring AC/DC voltage, resistance, capacitance, temperature, diode voltage drop, transistor hFE parameter, circuit continuity, square wave output and so on. Its adapter plug socket can conveniently test surface mount devices. UT132 can be used for home, schools, factories, electrical and chemical engineering, and other areas. It is a great tool for circuit maintenance and electrical equipment repair.

    SKU: n/a
  • UT136B+ Digital Multimeter

    0 out of 5
    (0)

    1. Measures up to 1000V and 10A AC/DC voltage and current

    2. Equipped with 3mm protective sleeve; 2 meters drop proof
    3. Large LCD display; Overload alarm
    4. Quick sampling rate, up to 4 times/s
    5. Quick capacitor measurement (measures 1mF in 4 seconds)
    6. Low power consumption and auto power saving function; long battery service life (>500hrs)
    SKU: n/a
  • YH 907C IRON FOR 853D2A

    0 out of 5
    (0)

    YH 907C IRON FOR 853D2A

    SKU: n/a
  • MRU-30 Earth Resistance and Resistivity Meter

    0 out of 5
    (0)

     

    • It allows to take the measurements of:

      • earthing resistance using auxiliary electrodes,
      • earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing),
      • earthing resistance using double clamps for measuring multiple earthing without underground connections.
      • ground resistivity (Wenner method),
      • continuity of equipotential bondings and protective
      • conductors (meeting the requirements IEC 60364) with auto-zero function – with current 200mA.

      Additionally:

      • measurement of resistance of auxiliary electrodes RS and RH,
      • measurement of interference voltage,
      • measurement in the presence of interference voltage in the power network
      • with frequency 50Hz, 60Hz,
      • selection of maximum measuring voltage (25V and 50V),
      • introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
      • memory of 990 measurements (10 banks of 99 cells each),
      • calibration of clamp used,
      • data transmission to the computer (USB),
      • indication of battery state.
    SKU: n/a