MRU-10 is a simple meter that allows you to measure grounding by the use of the technical method and to measure grounding resistance by the use of the 2-pole method. The instrument is easy to handle, resistive to interference, and highly accurate. MRU-10 is a basic device that allows checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments. The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.
MRU-10 Earth Resistance Meter
3 in stock
It allows to:
- measure earthing resistance using auxiliary electrodes,
- measurement of resistance of auxiliary electrodes RS and RH,
- measurement of interference voltage,
- measurement in the presence of interference voltage in the power network with frequency 50 Hz and 60 Hz,
- selection of maximum measuring voltage (25 V and 50 V),
- indication of battery state.
₨0
3 in stock
CompareWeight | 1 kg |
---|---|
Dimensions | 22 × 10 × 6 cm |
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(10% m.v. + 1 digit) |
Measurement of earthing resistance (method 3-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (for 50 V)
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(3% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200…1999 Ω | 1 Ω | ±5% m.v. |
2000…9999 Ω | 1 Ω | ±8% m.v. |
- measurement current: under short circuit >20 mA,
- voltage on open terminals: selectable 25 V AC or 50 V AC,
- frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz),
- selection of measuring frequency in settings.
Measurement of earthing resistance (method 2-pole)
Range | Resolution | Accuracy |
0,01…19,99 Ω | 0,01 Ω | ±(3% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200,0…1999 Ω | 1 Ω | ±5% m.v. |
2000…9999 Ω | 1 Ω | ±8% m.v. |
Measurement of earthing resistance (method 2-pole) RH and RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±8% m.v. |
1,00…9,99 kΩ | 0,01 Ω | |
10,0…19,9 kΩ | 0,1 Ω |
Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557,
- measurement category: CAT IV 150 V acc. to EN 61010-1,
- protection class acc. to EN 60529: IP67.
Rated operational conditions:
- operation temperature: -10…+50°C,
- storage temperature: -20…+60°C,
- humidity: 20…90%.
Other technical data:
- LCD display: segment, backlit,
- dimensions: 221 x 102 x 62 mm,
- number of measurements (RE3P) carried out of set of batteries: > 3000
Based on 0 reviews
Be the first to review “MRU-10 Earth Resistance Meter”
-
DC Power Supplies
DC Power Supply UTP3313TFL
Features:
1. Single channel, 3-bit digital display, shows voltage and current simultaneously
2. Voltage display resolution: 100mV; current display resolution: 10mA
3. Voltage output: 0~30V consecutive and adjustable voltage
4. Current output: 0~3A
5. Auto voltage and current stabilization conversion, current limiting protection, undamaged for any external usage
SKU: n/a -
Tool Kits
JM-TP03 Double Head Bits Set Screwdriver
Features:
- Set screwdriver
- Consists of 10 PZ2 type nut heads commonly used for electric screwdriver heads
- Equipped with a box to keep the screwdriver head with a lightweight design
- Has a very strong magnetic adhesive
- Material: Chrome vanadium
SKU: n/a -
-
Tool Kits, Tools and Hardware
JM-8101 Precision Screwdriver Tool Kit
Features:
- Adjustable screwdriver bits for different screws.
- Finest CR-V bits with HRC up to 52 ℃.
- Common used in precision work in electronics, DIY models, jewelry, eye glasses and other home appliances.
- Curved tip tweezer common used in mini electronic components.
- Portable box with transparent cover.
SKU: n/a
There are no reviews yet.