UT523A Earth Resistance Soil Resistivity Tester
Earth Ground Resistance Testers
UT523A Earth Resistance Soil Resistivity Tester
Availability:
3 in stock
UT523A Earth Resistance Soil Resistivity Tester
₨98,100 ₨111,875
3 in stock
CompareWeight | 1.5 kg |
---|---|
Dimensions | 21 × 19 × 9 cm |
Basic Functions | Range | Best Accuracy |
Model | UT523A | |
Earth resistance | 0.00Ω~19.99Ω | ±(2%+5) |
20.0Ω~199.9Ω | ±(2%+5) | |
200Ω~1999Ω | ±(2%+5) | |
2.00kΩ~19.99kΩ | ±(2%+5) | |
20.0kΩ~210.0kΩ | ±(2%+5) | |
Soil resistivity | 0.00Ωm~99.99Ωm | Decided by measuring precision of R: (ρ=2πaR a:1 m~100m, π=3.141) |
100.0Ωm~999.9Ωm | ||
1000Ωm~9999Ωm | ||
10.00kΩm~99.99kΩm | ||
100.0kΩm~999.9kΩm | ||
1000kΩm~9000kΩm | ||
Earth voltage | AC 0.00~750V | ±(2%+5) |
Testing resistance | 128Hz/111Hz/105Hz/94Hz(AFC) | √ |
Features | ||
Measuring method | Earth resistance: rated current pole changing method with Max 20mA measuring current; soil resistivity: quadrupole method (Wen-Na method ); earth voltage: average rectifier (between P(S) and ES interfaces) |
√ |
Short-circuit testing current | AC 30mA max | √ |
Open-circuit testing voltage | AC 40V max | √ |
Auto range | √ | |
Distance between electrodes | 1m~200m can be set. | √ |
Testing voltage waveform | Sine wave | √ |
Line voltage | Measure when the voltage is below 750V AC | √ |
Low battery indicator | ≤7.5V | √ |
Data hold | √ | |
Alarm function | √ | |
RS232 interface | √ | |
Withstand voltage | AC 3700V/rms(between circuit and case) | √ |
LCD backlight | √ | |
Data storage | 300 groups | √ |
Auxiliary earth resistance test | 0.00KΩ~30kΩ(100R+rC<50kΩ, 100R+rP<50kΩ) | √ |
Overload protection | Earth resistance measurement: input 280V AC between C(H) and E, P(S) and ES for 3s | √ |
Interference test | Auto identify interference signals, when interference voltage is higher than 5V, the symbole NOISE is displayed. | √ |
Measuring time(s) | More than 5000 times (perform short circuit test once, and again after 30s) | √ |
Insulation resistance | Above 20MΩ (500V between circuit and case) | √ |
General Characteristics | ||
Power supply | DC 9V (6 Zinc-manganese dry batteries, R14S 1.5V; can continuously standby for 300hrs) | |
LCD size | 128mm×75mm | |
Product color | Red and grey | |
Product weight | 1443g (including batteries) | |
Product size | 215mm×190mm×95mm | |
Standard accessories | Standard test lead, simple test lead, batteries, PC software CD, RS232 interface cable | |
Standard Individual Packing | Tool box, gift box, English manual, warranty card | |
Standard Quantity Per Carton | 4pcs | |
Standard Carton Measurement | 650mm×560mm×300mm | |
Standard Carton Cross Weight | 30kg (including batteries) |
Based on 0 reviews
Be the first to review “UT523A Earth Resistance Soil Resistivity Tester”
-
Multimeters
ET 8101 DMM
- Specifications: Brand Name: WinAPEX Color: Black Material: ABS Plastic Display: LCD Display with Backlight, 5999 counts(5 5/6) Range Control: Auto Range & Manual Range Screen Size: 48 * 30mm / 1.9 * 1.2in Operating Environment: IEC61010-1, CAT III 600V DC Voltage Range: 6V/60V/600V/1000V DC Voltage Resolution: 0.001V/0.01V/0.1V/1V AC Voltage Range: 6V/60V/600V/750V AC Voltage Resolution: 0.001V/0.01V/0.1V/1V DC Current Range: 600A/6000A/60mA/600mA/6A/10A DC Current
- Resolution: 0.1A/1A/10A/100A/0.01A AC Current Range: 600A/6000A/60mA/600mA/6A/10A AC Current Resolution: 0.1A/1A/10A/100A/0.01A Frequency Range: 10Hz/100Hz/1KHz/10KHz/100KHz/1MHz/10MHz Frequency Resolution: 0.01Hz/0.1Hz/1Hz/10Hz/100Hz/1kHz/10kHz Resistance Range: 600/6k/60k/600k/6M/40M Resistance Resolution: 0.1/1/10/100/1k/10k Capacitance Range: 60nF/600nF/6F/60F/600F/6mF/30mF Capacitance Resolution: 10pF/100pF/1nF/10nF/100nF/11F/10F Duty Cycle: 0.1%~99% Duty Cycle
- Resolution: 0.1% Function: DC/AC Voltage Current, Resistance, Capacitance, Data Hold, Max & Min Value Test, Backlight, Auto Power off, NCV Test, Continuity Buzzer Test with LCD, Over Load Protection, Short-circuit Protection, Live Fire Wire Identification, Frequency Test, Duty Cycle Measurement, Diode Test Sampling Time: about 3 times/second Working Temperature/Humidity: 0~40, <80% Storage Temperature/Humidity: -10~50, <70% Power Supply: 2 * 1.5V AAA Batteries
- (Not Included) Item Size: 145 * 70 * 32mm / 5.7 * 2.8 * 1.3in Item Weight: 166g / 5.9oz
SKU: n/a -
Function Generators
UTG2025A Function/Arbitrary Waveform Generator
1. 1μHz full-band resolution
2. 5MHz~30MHz pulse waveform, adjustable rise/fall time3. 14-bit/16-bit vertical resolution4. Two equivalent-performance channels5. Max arbitrary waveform length of 8k/16M points; 48/1616. non-volatile waveforms storageSKU: n/a -
Earth Ground Resistance Testers
UT278A Clamp Earth Ground Testers
UT270 series is widely used in earth ground and circuit resistance measurements of electric power, telecommunications, meteorology, oil field, construction and industrial electrical equipment. It can measure the ground system of the circuit without disconnecting grounding wires, auxiliary electrode. UT278A can also measure leakage current and neutralline current of earth ground system
.SKU: n/a