MRU-10 Earth Resistance Meter

Availability:

3 in stock


It allows to:

  • measure earthing resistance using auxiliary electrodes,
  • measurement of resistance of auxiliary electrodes RS and RH,
  • measurement of interference voltage,
  • measurement in the presence of interference voltage in the power network with frequency 50 Hz and 60 Hz,
  • selection of maximum measuring voltage (25 V and 50 V),
  • indication of battery state.

0

3 in stock

Compare

MRU-10 is a simple meter that allows you to measure grounding by the use of the technical method and to measure grounding resistance by the use of the 2-pole method. The instrument is easy to handle, resistive to interference, and highly accurate. MRU-10  is a basic device that allows checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments. The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.

Weight 1 kg
Dimensions 22 × 10 × 6 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of earthing resistance (method 3-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (for 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.
  • measurement current: under short circuit >20 mA,
  • voltage on open terminals: selectable 25 V AC or 50 V AC,
  • frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz),
  • selection of measuring frequency in settings.

Measurement of earthing resistance (method 2-pole)

Range Resolution Accuracy
0,01…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

Measurement of earthing resistance (method 2-pole) RH and RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±8% m.v.
1,00…9,99 kΩ 0,01 Ω
10,0…19,9 kΩ 0,1 Ω

Electric security:

  • type of insulation: double, according to EN 61010-1 and IEC 61557,
  • measurement category: CAT IV 150 V acc. to EN 61010-1,
  • protection class acc. to EN 60529: IP67.

Rated operational conditions:

  • operation temperature: -10…+50°C,
  • storage temperature: -20…+60°C,
  • humidity: 20…90%.

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 221 x 102 x 62 mm,
  • number of measurements (RE3P) carried out of set of batteries: > 3000

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-10 Earth Resistance Meter”

There are no reviews yet.

  • MS 2109A ACA DCA Digital Clamp Meters

    0 out of 5
    (0)

    ● Display 6000 counts
    ● Jaw Opening Ф26mm/1.0″
    ● Auto Ranging
    ● Auto Power Off
    ● Non-Contact Voltage Detector
    ● Relative Measurement
    ● Diode Open Volatge  2.7V
    ● Continuity Buzzer  <50±20Ω
    ● MAX/MIN
    ● Data Hold
    ● Display Backlight
    ● Work Light
    ● Low Battery Display

    SKU: n/a
  • CMP-400 Digital Clamp-On Multimeter

    0 out of 5
    (0)

    Additionally:

    • safe, insulated measuring clamps,
    • double molded housing,
    • autoranging/manual range selection,
    • DATA HOLD function, for holding measured values,
    • backlit LCD,
    • REL function,
    • over range indication,
    • AUTO-OFF function.
    SKU: n/a
  • RF-7050PRo

    0 out of 5
    (0)
    SKU: n/a
  • UT219M ACA Professional Clamp Meters with Motor Test

    0 out of 5
    (0)
    • UT-219 professional clamp meter series is three-proofing digital clamp meter specially designed for professional industrial users.
    •  The industrial design of this series is rugged and durable, and capable of withstanding the impact from 2 meters fall-down.
    • The waterproof rating is up to IP54; therefore, it can be used in environment with water splashing or much more dust. The whole series is configured with LoZ (Low Impedance Input) AC voltage tap position, which is capable of testing the false voltage; auto backlight function can be used continuously under the circumstance of emergency power outage. UT-219M is also provided with MOTOR test function, allowing to directly test the phase sequence of three phase AC motor by means of the probe. UT-219 series is much more in compliance with CAT IV 600V safety level, and certified by the German GS institution.
    SKU: n/a