MRU-10 Earth Resistance Meter

Availability:

3 in stock


It allows to:

  • measure earthing resistance using auxiliary electrodes,
  • measurement of resistance of auxiliary electrodes RS and RH,
  • measurement of interference voltage,
  • measurement in the presence of interference voltage in the power network with frequency 50 Hz and 60 Hz,
  • selection of maximum measuring voltage (25 V and 50 V),
  • indication of battery state.

0

3 in stock

Compare

MRU-10 is a simple meter that allows you to measure grounding by the use of the technical method and to measure grounding resistance by the use of the 2-pole method. The instrument is easy to handle, resistive to interference, and highly accurate. MRU-10  is a basic device that allows checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments. The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.

Weight 1 kg
Dimensions 22 × 10 × 6 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of earthing resistance (method 3-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (for 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.
  • measurement current: under short circuit >20 mA,
  • voltage on open terminals: selectable 25 V AC or 50 V AC,
  • frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz),
  • selection of measuring frequency in settings.

Measurement of earthing resistance (method 2-pole)

Range Resolution Accuracy
0,01…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

Measurement of earthing resistance (method 2-pole) RH and RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±8% m.v.
1,00…9,99 kΩ 0,01 Ω
10,0…19,9 kΩ 0,1 Ω

Electric security:

  • type of insulation: double, according to EN 61010-1 and IEC 61557,
  • measurement category: CAT IV 150 V acc. to EN 61010-1,
  • protection class acc. to EN 60529: IP67.

Rated operational conditions:

  • operation temperature: -10…+50°C,
  • storage temperature: -20…+60°C,
  • humidity: 20…90%.

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 221 x 102 x 62 mm,
  • number of measurements (RE3P) carried out of set of batteries: > 3000

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-10 Earth Resistance Meter”

There are no reviews yet.

  • RF-0.48x

    0 out of 5
    (0)
    SKU: n/a
  • UT-L21 Probe UT-L Probes and Test Leads

    0 out of 5
    (0)

    Leads length: 900mm

    Rod length: 133mm
    Tip length: 15.8mm
    Safety level: CAT Ⅲ 1000V/CAT Ⅳ 600V 20A
    Features and application: cross plug with shield sleeve, general type probe
    Amount: 1PCS

    SKU: n/a
  • ,

    Mechanic T12 Pro Intelligent Temperature Control Anti-Static Soldering Station

    0 out of 5
    (0)
      • Intelligent digital display
      • 450°C high temperature
      • Heat up in 4 seconds
      • Regular dormancy
      • Small and portable
      • Safe and convenient
    SKU: n/a
  • UTD2052CL Digital Storage Oscilloscope

    0 out of 5
    (0)

    1. Dual analog channels width range 1mV/div~20V/div;
    2. 7 inches widescreen LCD displays;
    3. Special Print Scree Feature;
    4. Supports plug-and-play USB storage device. Communication with and remote control of computer through the USB device;
    5. USB drive system software upgrade;
    6. Storage of waveforms setups and interfaces waveforms and setups reproduction;
    7. Automatic measurement of 28 waveform parameters;
    8. Unique waveform recording and replay function;
    9. Multilingual menu displays.

    SKU: n/a
  • MRU-21 Earth Resistance Meter

    0 out of 5
    (0)

    Possible measurements:

    • earth resistance measurment with 3-pole method,
    • measurement of continuity of equipotential bondings and protective conductors with auto-zero function – with current 200 mA,
    • resistance measurement using 2-pole method.
    SKU: n/a