MRU-10 Earth Resistance Meter

Availability:

3 in stock


It allows to:

  • measure earthing resistance using auxiliary electrodes,
  • measurement of resistance of auxiliary electrodes RS and RH,
  • measurement of interference voltage,
  • measurement in the presence of interference voltage in the power network with frequency 50 Hz and 60 Hz,
  • selection of maximum measuring voltage (25 V and 50 V),
  • indication of battery state.

0

3 in stock

Compare

MRU-10 is a simple meter that allows you to measure grounding by the use of the technical method and to measure grounding resistance by the use of the 2-pole method. The instrument is easy to handle, resistive to interference, and highly accurate. MRU-10  is a basic device that allows checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments. The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.

Weight 1 kg
Dimensions 22 × 10 × 6 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of earthing resistance (method 3-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (for 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.
  • measurement current: under short circuit >20 mA,
  • voltage on open terminals: selectable 25 V AC or 50 V AC,
  • frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz),
  • selection of measuring frequency in settings.

Measurement of earthing resistance (method 2-pole)

Range Resolution Accuracy
0,01…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

Measurement of earthing resistance (method 2-pole) RH and RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±8% m.v.
1,00…9,99 kΩ 0,01 Ω
10,0…19,9 kΩ 0,1 Ω

Electric security:

  • type of insulation: double, according to EN 61010-1 and IEC 61557,
  • measurement category: CAT IV 150 V acc. to EN 61010-1,
  • protection class acc. to EN 60529: IP67.

Rated operational conditions:

  • operation temperature: -10…+50°C,
  • storage temperature: -20…+60°C,
  • humidity: 20…90%.

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 221 x 102 x 62 mm,
  • number of measurements (RE3P) carried out of set of batteries: > 3000

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-10 Earth Resistance Meter”

There are no reviews yet.

  • UTG9005C-II Function/Arbitrary Waveform Generato

    0 out of 5
    (0)

    1. Output waveforms: Sine, square, ramp, pulse, noise, DC, arbitrary

    2. Output frequency range: Sine/square, 5MHz
    3. High-accuracy, broad-band 6 bit frequency counter, range: 100mHz~100MHz
    4. 4W power output
    5. EBTN LCD screen
    SKU: n/a
  • UT233 Digital Power Clamp Meters

    0 out of 5
    (0)

    UT 230 series is a handheld intelligent power clamp meter, which combines with digital current meter and power meter. It is equipped with powerful measurement and data processing software, which can help complete measurements, calculations and displays of voltage, current, active power, power factor, phase angle, apparent power, reactive power, power, frequency, temperature and other parameters.

    SKU: n/a
  • UT60S

    0 out of 5
    (0)
    1. 9999 counts
    2. True RMS
    3. Bluetooth
    4. Duty cycle
    5. Diode/Continuity test
    6. Temperature
    7. Non-contact voltage
    8. Analog bar/Data hold
    9. Backlight/Relative mode
    10. Auto/Manual range
    11. Low battery indication
    12. Three-color LED light indicator