Earth Resistance Meter
MRU-21 Earth Resistance Meter
2 in stock
Possible measurements:
- earth resistance measurment with 3-pole method,
- measurement of continuity of equipotential bondings and protective conductors with auto-zero function – with current 200 mA,
- resistance measurement using 2-pole method.
₨0
2 in stock
CompareWeight | 1.4 kg |
---|---|
Dimensions | 29 × 22 × 7 cm |
Measurement of earthing resistance
measurement range to IEC61557 – 5:
0,50 Ω…1,99 kΩ for Un=50 V;
0,68 Ω…1,99 kΩ for Un=25 V;
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…999 Ω | 1 Ω | |
1,00k…1,99 kΩ | 0,01 kΩ |
• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable <25 V AC or <50 V AC,
• frequency of measurement current: 125 Hz
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(2% m.v. + 3 digits) |
• measurement for DC and AC 45…65 Hz
Measurement of resistance of auxiliary electrodes RH i RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±(5% (RS+RE+RH) + 3 digits) |
1,00k…9,99 kΩ | 0,01 kΩ | |
10,0k…50,0 kΩ | 0,1 kΩ |
Measuremet of continuity of equipotential bondings and protective conductors
measurement range to IEC61557 – 4: 0,13 Ω…199 Ω
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…199 Ω | 1 Ω |
- measuring method: technical 2-pole method,
- max. voltage on open terminals: 13 V,
- measurement current: under short circuit >200 mA,
- auto-zero function for measurement leads
Electric security:
- type of insulation: double, according to EN 61010 – 1and IEC 61557
- measurement category: CAT IV 300 V acc. to EN 61010 – 1
- protection class acc. to EN 60529: IP54
Rated operational conditions:
- operation temperature: -10…+55°C
- storage temperature: -20…+70°C
- humidity: 20…80%
Other technical data:
- LCD display: segment, backlit
- interface: USB,
- number of measurements carried out of set of batteries: > 1000 (5 Ω, 2 meas./min.)
- warranty: 2 years
- dimentions: 288 x 223×75 mm
- weigth: 1,4 kg
Based on 0 reviews
Be the first to review “MRU-21 Earth Resistance Meter”
-
-
Clamp Meters
UT219DS ACA DCA Professional Clamp Meters with Motor LPF Test
- UT-219 professional clamp meter series is three-proofing digital clamp meter specially designed for professional industrial users.
- The industrial design of this series is rugged and durable, and capable of withstanding the impact from 2 meters fall-down.
- The waterproof rating is up to IP54; therefore, it can be used in environment with water splashing or much more dust.
- The whole series is configured with LoZ (Low Impedance Input) AC voltage tap position, which is capable of testing the false voltage; auto backlight function can be used continuously under the circumstance of emergency power outage.
- UT-219DS is also provided with MOTOR test function, allowing to directly test the phase sequence of three phase AC motor by means of the probe. UT-219 series is much more in compliance with CAT IV 600V safety level, and certified by the German GS institution.
SKU: n/a -
Multimeters
UT890C+ TRMS Digital Multimeter
1.6000 Counts; Measure voltage and current RMS.
2.The capacitance slot has REL function. Range is from 1pF to 99.99mF
3.The device can measure frequency of high accuracy. The min resolution is 0.001Hz4.It has special functions: MAX/MIN and MAX-MIN
5.The min DC and AC resolution is 0.01μA and 1μA. The max range is 20A.
6.It can measure diode whose voltage drop is up to 3V .So it is very suitable to measure LED.
7.It has functions: hold, power off and backlight.
8.It also measure temperature ℃ and ℉SKU: n/a
There are no reviews yet.