MRU-30 Earth Resistance and Resistivity Meter

Availability:

3 in stock


 

  • It allows to take the measurements of:

    • earthing resistance using auxiliary electrodes,
    • earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing),
    • earthing resistance using double clamps for measuring multiple earthing without underground connections.
    • ground resistivity (Wenner method),
    • continuity of equipotential bondings and protective
    • conductors (meeting the requirements IEC 60364) with auto-zero function – with current 200mA.

    Additionally:

    • measurement of resistance of auxiliary electrodes RS and RH,
    • measurement of interference voltage,
    • measurement in the presence of interference voltage in the power network
    • with frequency 50Hz, 60Hz,
    • selection of maximum measuring voltage (25V and 50V),
    • introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
    • memory of 990 measurements (10 banks of 99 cells each),
    • calibration of clamp used,
    • data transmission to the computer (USB),
    • indication of battery state.

0

3 in stock

Compare

The Sonel MRU-30 uses most known methods of earth resistance measurements. Tests can be performed using the 3-pole, 4-pole, 3-pole with auxiliary clamp and also, additionally, the MRU-30 employs the two clamp method of measurement, without the use of auxiliary test rods which can’t be used in some situations. Complementary features of the MRU-30 are measurements of soil resistivity, continuity measurement of protective and equipotential conductors and, using clamps, leakage currents and interference voltages.

  • Robust and weatherproof (IP65) – no ingress of dust, water protected by a nozzle against enclosure from any direction.
  • Ergonomic casing – small and handy casing to make the measurements more convenient than before.
  • Built-in rechargeable battery – saving time to replace flat batteries; can be recharged from Power Bank and Cigarette Lighter Socket!
  • Clear on-screen notes – displayed on screen before and after the measurement to alert user of possible dangers and irregularities.
  • Many measurement methods available in a small, portable casing
Weight 5 kg
Dimensions 20 × 15 × 7 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC 61557-4:2007: 0,13 Ω…1999 Ω

Range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
10,0…99,9 Ω 0,1 Ω
100…1999 Ω 1 Ω

• measurement current: under short circuit >200mA
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)

Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (dla 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz).

Measurement of multiple earthing esistance with using the clamp and auxiliary electrodes (3p + clamp)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• voltage on open terminals: selectable 25 V AC or 50 V AC,
• measurement current: under short circuit >20 mA,
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of resistance of auxiliary electrodes RH i RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±(5% m.v.+ 8 digits)
1,00k…9,99 kΩ 0,01 kΩ
10,0k…19,9 kΩ 0,1 kΩ

 

Measurement of multiple earthing resistance with using double clamps

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(10% m.v. + 8 digits)
20,0…99,9 Ω 0,1 Ω ±(20% m.v. + 3 digits)

• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz
(for networks 60 Hz)

Measurement of ground resistivity 
Measurement method: Wenner, ρ=2πLRE

Range Resolution Accuracy
0,00…9,99 Ωm 0,01 Ωm depending on measurement
accuracy RE with 4p method,
but not less than ±1 digit
10,0…99,9 Ωm 0,1 Ωm
100…999 Ωm 1 Ωm
1,00…9,99 kΩm 0,01 kΩm
10,0…99,9 kΩm 0,1 kΩm
100…999 kΩm 1 kΩm

L – distance between probes: 1…50 m.. or 1…150 ft

Electric security:

  • type of insulation: double, according to EN 61010-1 i IEC 61557,
  • measurement category: CAT III 300V wg EN 61010-1,
  • protection class acc. to EN 60529: IP65,

Rated operational conditions:

  • operation temperature: -10…+55°C,
  • storage temperature: -20…+80°C,
  • humidity: 20…90%,

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 200x150x74 mm.

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-30 Earth Resistance and Resistivity Meter”

There are no reviews yet.

  • UNI T Bench Top Digital Multimeter UT8803E

    0 out of 5
    (0)
    1. 20,000 Count EBTN LCD Display
    2. DC Voltage: 200mV/2V/20V/200V/1000V
    3. AC Voltage: 2V/20V/200V/750V
    4. DC Current: 200μA/2mA/20mA/200mA/20A
    5. AC Current: 2mA/20mA/200mA/20A
    6. Resistance: 200Ω/2kΩ/20kΩ/200kΩ/2MΩ/200MΩ
    7. Capacitance: 20nF/200nF/2μF/20μF/200μF/2mF/20mF/100mF
    8. Frequency: 200Hz~10MHz
    9. Duty cycle: 5%~99%
    10. Frequency response: 1 kHz
    11. USB Interface
    12. Data hold
    13. MAX/MIN
    14. Continuity buzzer
    15. Diode/transistor
    16. test
    17. CAT II 600V
    SKU: n/a
  • UT705 Single Function Loop Calibrator

    0 out of 5
    (0)

    1. Measures: DC voltage, DC current, 4-20mA loop current

    2. Output functions: DC current, analog transmitter, 24V loop
    3. Up to 0.02% accuracy current measurement at the same time
    4. Automatic ramp for DC current output
    5. Manual stepping and automatic stepping and  ramping output
    6. Stores and recalls setups
    SKU: n/a
  • UT285C Three Phase Power Quality Analyzer

    0 out of 5
    (0)

    1. Waveform real-time display (4 channels voltage/4 channels current).

    2. True RMS values of voltages and currents
    3. Peak current and voltage values
    4. Total harmonic distortion (THD)
    5. Active, reactive, apparent power, by phase and cumulative
    6. Transformer K factor
    7. Power factors (PF) and displacement factors (DPF or COSΦ)
    8. Short-term voltage flicker (PST)
    9. Three phase unbalance(current and voltage)
    10. USB interface/PC software
    SKU: n/a
  • ,

    JM-6111 Professional Screwdriver Tool Set

    0 out of 5
    (0)

     

    Features:

    • Ratchet screwdrivers with twist reverse and ratchet lock mechanism.
    • Contoured comfort grip handle. Supplied in a portable box.
    • Adjustable screwdriver bits for different screws.
    • Common used in automotive parts and home appliances.
    • Non-slip handle is made of PP & TPR material.
    SKU: n/a
  • YIHUA 936 Soldering Station

    0 out of 5
    (0)

    Application Scope


    1. Production lines for electronic products , suitable for desoldering of small solder joints ,components.
      2. Repair industry for moblie phone.
      3. SMD components requiring the highest precision
    SKU: n/a