MRU-30 Earth Resistance and Resistivity Meter

Availability:

3 in stock


 

  • It allows to take the measurements of:

    • earthing resistance using auxiliary electrodes,
    • earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing),
    • earthing resistance using double clamps for measuring multiple earthing without underground connections.
    • ground resistivity (Wenner method),
    • continuity of equipotential bondings and protective
    • conductors (meeting the requirements IEC 60364) with auto-zero function – with current 200mA.

    Additionally:

    • measurement of resistance of auxiliary electrodes RS and RH,
    • measurement of interference voltage,
    • measurement in the presence of interference voltage in the power network
    • with frequency 50Hz, 60Hz,
    • selection of maximum measuring voltage (25V and 50V),
    • introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
    • memory of 990 measurements (10 banks of 99 cells each),
    • calibration of clamp used,
    • data transmission to the computer (USB),
    • indication of battery state.

0

3 in stock

Compare

The Sonel MRU-30 uses most known methods of earth resistance measurements. Tests can be performed using the 3-pole, 4-pole, 3-pole with auxiliary clamp and also, additionally, the MRU-30 employs the two clamp method of measurement, without the use of auxiliary test rods which can’t be used in some situations. Complementary features of the MRU-30 are measurements of soil resistivity, continuity measurement of protective and equipotential conductors and, using clamps, leakage currents and interference voltages.

  • Robust and weatherproof (IP65) – no ingress of dust, water protected by a nozzle against enclosure from any direction.
  • Ergonomic casing – small and handy casing to make the measurements more convenient than before.
  • Built-in rechargeable battery – saving time to replace flat batteries; can be recharged from Power Bank and Cigarette Lighter Socket!
  • Clear on-screen notes – displayed on screen before and after the measurement to alert user of possible dangers and irregularities.
  • Many measurement methods available in a small, portable casing
Weight 5 kg
Dimensions 20 × 15 × 7 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC 61557-4:2007: 0,13 Ω…1999 Ω

Range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
10,0…99,9 Ω 0,1 Ω
100…1999 Ω 1 Ω

• measurement current: under short circuit >200mA
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)

Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (dla 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz).

Measurement of multiple earthing esistance with using the clamp and auxiliary electrodes (3p + clamp)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• voltage on open terminals: selectable 25 V AC or 50 V AC,
• measurement current: under short circuit >20 mA,
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of resistance of auxiliary electrodes RH i RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±(5% m.v.+ 8 digits)
1,00k…9,99 kΩ 0,01 kΩ
10,0k…19,9 kΩ 0,1 kΩ

 

Measurement of multiple earthing resistance with using double clamps

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(10% m.v. + 8 digits)
20,0…99,9 Ω 0,1 Ω ±(20% m.v. + 3 digits)

• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz
(for networks 60 Hz)

Measurement of ground resistivity 
Measurement method: Wenner, ρ=2πLRE

Range Resolution Accuracy
0,00…9,99 Ωm 0,01 Ωm depending on measurement
accuracy RE with 4p method,
but not less than ±1 digit
10,0…99,9 Ωm 0,1 Ωm
100…999 Ωm 1 Ωm
1,00…9,99 kΩm 0,01 kΩm
10,0…99,9 kΩm 0,1 kΩm
100…999 kΩm 1 kΩm

L – distance between probes: 1…50 m.. or 1…150 ft

Electric security:

  • type of insulation: double, according to EN 61010-1 i IEC 61557,
  • measurement category: CAT III 300V wg EN 61010-1,
  • protection class acc. to EN 60529: IP65,

Rated operational conditions:

  • operation temperature: -10…+55°C,
  • storage temperature: -20…+80°C,
  • humidity: 20…90%,

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 200x150x74 mm.

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-30 Earth Resistance and Resistivity Meter”

There are no reviews yet.

  • MIC-2501,2500V Insulation Resistance Meter

    0 out of 5
    (0)

     

    Electrical safety:

    • type of insulation: double, in acc. with EN 61010-1 und IEC 61557
    • measurement category: IV 600 V (III 1000 V) in acc. to EN 61010-1
    • case protection rating in acc. with EN 60529: IP65

    Other technical specifications:

    • power supply of the meter SONEL L-1 NiMH 9,6 V; DC 12 V 2,5 A
    • weight of the meter: approx. 0,9 kg
    • dimensions: 200 x 180 x 77 mm
    • display: LCD segment display
    • measurement results memory: 990 cells, 11880 records,
    • transmission of measurement results: USB
    SKU: n/a
  • TND 2000VA

    0 out of 5
    (0)

    Input Voltage=140-250
    Output Voltage=220
    Copper Wind
    Analog Display
    Under and Over Volt Indication
    Under Volt Protection
    Dual Output Socket 110/220

    SKU: n/a
  • CLAMP METER AC DC CM 2056

    0 out of 5
    (0)

    Technical data

    Basic function

    Range

    Accuracy

    DCV

    400mV/4V/40V/400V/1000V

    ±(0.5%+5)

    ACV

    400mV/4V/40V/400V/750V

    ±(1.0%+5)

    DCA

    400A/1000A

    ±(2.0%+5)

    ACA

    400A/1000A

    ±(2.0%+5)

    Resistance

    400Ω/4kΩ/40kΩ/400kΩ/4MΩ/40MΩ

    ±(0.8%+3)

    Capacitance

    4nF/40nF/400nF/4uF/40uF/200uF

    ±(3.5%+8)

    Frequency

    100Hz/1kHz/10kHz/100kHz/1MHz/10MHz

    ±(0.5%+4)

    Temperature

    (-40~ 1000) ℃ / (-40 ~1832) ℉

    ±(1.0%+5)

    Special function

    CM-2056

    NCV test

    True RMS test

    Diode test

    Continuity test

    Less than 50Ω±10Ω

    Low battery indicator

    Approx. less than 2.4 V

    Data hold

    Auto power off

    About 15 minutes

    Function protection

    Clamp light

    Backlight display

    Input impedance

    10MΩ

    Sampling rate

    3 times/s

    AC frequency response

    Current 50-60Hz/ voltage 50-400Hz

    Operation method

    Auto or manual range

    Max display

    4000

    Clamp opens

    52mm

    Battery

    3V (2*AAA battery)

    General Characteristic

    Meter color

    Orange and Black

    Meter weight

    About 280g (including battery)

    Meter size

    270×123×50mm

    Standard accessory

    Test leads, battery, manual, TP01 temperature probe

    SKU: n/a
  • UTG1005A Function/Arbitrary Waveform Generator

    0 out of 5
    (0)

    1. Intuitive interface design

    2. Single channel
    3. 125MS/s sampling rate, 14-bit vertical resolution
    4. Integrated analog and digital design
    5. 4.3 inches TFT LCD
    SKU: n/a
  • DIGITAL INSULATION / CONTINUITY TESTER MODEL 3007A

    0 out of 5
    (0)

    • Bargraph to display insulation resistance.
    • Displays the value of external AC voltage along with flashing symbol.
    • Auto null function to automatically subtract the test lead resistance before displaying the real continuity resistance value.
    • Trac-Lok mode to conserve battery life on insulation and continuity tests.
    • Live circuit warning beeper.
    • Releasing the test button automatically discharges the charges stored in the circuit under test.
    • Backlight function to view the test results in dimly lit areas.
    • 200mA continuity measuring current to IEC 61557.
    • Minimum 1mA current on insulation tests to IEC 61557.

    SKU: n/a