  • It allows to take the measurements of:

    • earthing resistance using auxiliary electrodes,
    • earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing),
    • earthing resistance using double clamps for measuring multiple earthing without underground connections.
    • ground resistivity (Wenner method),
    • continuity of equipotential bondings and protective
    • conductors (meeting the requirements IEC 60364) with auto-zero function – with current 200mA.

    Additionally:

    • measurement of resistance of auxiliary electrodes RS and RH,
    • measurement of interference voltage,
    • measurement in the presence of interference voltage in the power network
    • with frequency 50Hz, 60Hz,
    • selection of maximum measuring voltage (25V and 50V),
    • introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
    • memory of 990 measurements (10 banks of 99 cells each),
    • calibration of clamp used,
    • data transmission to the computer (USB),
    • indication of battery state.

0

3 in stock

Compare

The Sonel MRU-30 uses most known methods of earth resistance measurements. Tests can be performed using the 3-pole, 4-pole, 3-pole with auxiliary clamp and also, additionally, the MRU-30 employs the two clamp method of measurement, without the use of auxiliary test rods which can’t be used in some situations. Complementary features of the MRU-30 are measurements of soil resistivity, continuity measurement of protective and equipotential conductors and, using clamps, leakage currents and interference voltages.

  • Robust and weatherproof (IP65) – no ingress of dust, water protected by a nozzle against enclosure from any direction.
  • Ergonomic casing – small and handy casing to make the measurements more convenient than before.
  • Built-in rechargeable battery – saving time to replace flat batteries; can be recharged from Power Bank and Cigarette Lighter Socket!
  • Clear on-screen notes – displayed on screen before and after the measurement to alert user of possible dangers and irregularities.
  • Many measurement methods available in a small, portable casing
Weight 5 kg
Dimensions 20 × 15 × 7 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC 61557-4:2007: 0,13 Ω…1999 Ω

Range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
10,0…99,9 Ω 0,1 Ω
100…1999 Ω 1 Ω

• measurement current: under short circuit >200mA
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)

Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (dla 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz).

Measurement of multiple earthing esistance with using the clamp and auxiliary electrodes (3p + clamp)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• voltage on open terminals: selectable 25 V AC or 50 V AC,
• measurement current: under short circuit >20 mA,
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of resistance of auxiliary electrodes RH i RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±(5% m.v.+ 8 digits)
1,00k…9,99 kΩ 0,01 kΩ
10,0k…19,9 kΩ 0,1 kΩ

 

Measurement of multiple earthing resistance with using double clamps

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(10% m.v. + 8 digits)
20,0…99,9 Ω 0,1 Ω ±(20% m.v. + 3 digits)

• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz
(for networks 60 Hz)

Measurement of ground resistivity 
Measurement method: Wenner, ρ=2πLRE

Range Resolution Accuracy
0,00…9,99 Ωm 0,01 Ωm depending on measurement
accuracy RE with 4p method,
but not less than ±1 digit
10,0…99,9 Ωm 0,1 Ωm
100…999 Ωm 1 Ωm
1,00…9,99 kΩm 0,01 kΩm
10,0…99,9 kΩm 0,1 kΩm
100…999 kΩm 1 kΩm

L – distance between probes: 1…50 m.. or 1…150 ft

Electric security:

  • type of insulation: double, according to EN 61010-1 i IEC 61557,
  • measurement category: CAT III 300V wg EN 61010-1,
  • protection class acc. to EN 60529: IP65,

Rated operational conditions:

  • operation temperature: -10…+55°C,
  • storage temperature: -20…+80°C,
  • humidity: 20…90%,

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 200x150x74 mm.

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-30 Earth Resistance and Resistivity Meter”

There are no reviews yet.

  • ET 8101 DMM

    0 out of 5
    (0)
    • Specifications: Brand Name: WinAPEX Color: Black Material: ABS Plastic Display: LCD Display with Backlight, 5999 counts(5 5/6) Range Control: Auto Range & Manual Range Screen Size: 48 * 30mm / 1.9 * 1.2in Operating Environment: IEC61010-1, CAT III 600V DC Voltage Range: 6V/60V/600V/1000V DC Voltage Resolution: 0.001V/0.01V/0.1V/1V AC Voltage Range: 6V/60V/600V/750V AC Voltage Resolution: 0.001V/0.01V/0.1V/1V DC Current Range: 600A/6000A/60mA/600mA/6A/10A DC Current
    • Resolution: 0.1A/1A/10A/100A/0.01A AC Current Range: 600A/6000A/60mA/600mA/6A/10A AC Current Resolution: 0.1A/1A/10A/100A/0.01A Frequency Range: 10Hz/100Hz/1KHz/10KHz/100KHz/1MHz/10MHz Frequency Resolution: 0.01Hz/0.1Hz/1Hz/10Hz/100Hz/1kHz/10kHz Resistance Range: 600/6k/60k/600k/6M/40M Resistance Resolution: 0.1/1/10/100/1k/10k Capacitance Range: 60nF/600nF/6F/60F/600F/6mF/30mF Capacitance Resolution: 10pF/100pF/1nF/10nF/100nF/11F/10F Duty Cycle: 0.1%~99% Duty Cycle
    • Resolution: 0.1% Function: DC/AC Voltage Current, Resistance, Capacitance, Data Hold, Max & Min Value Test, Backlight, Auto Power off, NCV Test, Continuity Buzzer Test with LCD, Over Load Protection, Short-circuit Protection, Live Fire Wire Identification, Frequency Test, Duty Cycle Measurement, Diode Test Sampling Time: about 3 times/second Working Temperature/Humidity: 0~40, <80% Storage Temperature/Humidity: -10~50, <70% Power Supply: 2 * 1.5V AAA Batteries
    • (Not Included) Item Size: 145 * 70 * 32mm / 5.7 * 2.8 * 1.3in Item Weight: 166g / 5.9oz
    SKU: n/a
  • JM OP018 OPENING TOOL

    0 out of 5
    (0)
    SKU: n/a
  • Jakemy JM-6107 79 in 1 Screwdriver Set

    0 out of 5
    (0)

    Main Features:
    ● Universal screwdriver tool kit
    ● Highly precise tips in various specifications for different uses
    ● Non-slip rubber design handle for a secure and comfortable grip, easy to operate
    ● Great for mobile phone, PDA, PC and other applications, portable case

    SKU: n/a
  • CMM-11 Multimeter

    0 out of 5
    (0)
    • manual and automatic range selection
    • HOLD function for holding measured values
    • MAX/MIN” function for displaying extreme values
    • compact housing  – allows to store the device in a pocket
    • increased resistance to falls from heights above 2 m thanks to the elastomer coating
    • built-in Bluetooth module for data transfer to mobile devices
    • built-in flashlight for lighting the measuring places
    • Beeper for sound signal circuit continuity
    • Auto-OFF function for automatic switching off of the unused device
    • display 3¾ digit (count max 4000)