UT270 series can measure the grounding system of a circuit without disconnecting the ground wires and auxiliary electrode. It clamps the grounding circuit and measures the grounding resistance fast and safely. It can measure resistance as low as 0.01Ω and has a high resolution of 0.001Ω. It has overload alarm function, which can help to setup the alarm value within the ranges. The clamp has double insulation, which strengthens the anti-interference.
UT275 Clamp Earth Ground Testers
Out of stock
UT270 series can measure the grounding system of a circuit without disconnecting the ground wires and auxiliary electrode. It clamps the grounding circuit and measures the grounding resistance fast and safely. It can measure resistance as low as 0.01Ω and has a high resolution of 0.001Ω. It has overload alarm function, which can help to setup the alarm value within the ranges. The clamp has double insulation, which strengthens the anti-interference.
₨94,800 ₨96,000
Out of stock
CompareWeight | 1.3 kg |
---|---|
Dimensions | 29 × 9 × 7 cm |
Specifications | Range | Best Accuracy |
Model | UT275 | |
Earth Ground Resistance (Ω) | 0.01~0.099Ω | ±(1%+0.01) |
0.1~0.99Ω | ±(1%+0.01) | |
1.0~49.9Ω | ±(1.5%+0.1) | |
50.0~99.5Ω | ±(2%+0.5) | |
100~199Ω | ±(3%+1) | |
200~395Ω | ±(10%+5) | |
400~590Ω | ±(20%+10) | |
600~1000Ω | ±(25%+20) | |
Leakage Current(A) | 0.00~299mA | ±(2.5%+2mA) |
0.30~2.99A | ±(2.5%+100mA) | |
3.00~30.0A | ±(2.5%+300mA) | |
Features | ||
Display Count | 9999 | |
Auto Range | √ | |
Jaw Capacity | 28mm | |
Auto Power Off | √ | |
Low Battery Indication | ≤5.2V | √ |
Data Hold | √ | |
Data Logging | 30 | |
Data Recall | √ | |
LCD Backlight | √ | |
Auto Calibration | √ | |
Resistance Limit Alarm | √ | |
General Characteristic | ||
Power | 1.5V Alkaline Batteries(LR6)×4 | |
LCD Size | 47mm X 28.5 mm | |
Product Color | Red and Grey | |
Product Net Weight | 1320g | |
Product Size | 293mm X 90mm X66 mm | |
Standard Accessories | Batteries, Test Ring, Tool Box | |
Standard Individual Packing | Gift Box, English Manual | |
Standard Quantity Per Carton | 5 PCs | |
Standard Carton Measurement | 495mm X 368mm X 310mm (0.057CBM Per Standard Carton) | |
Standard Carton Gross Weight | 16Kg |
Based on 0 reviews
Be the first to review “UT275 Clamp Earth Ground Testers”
-
Oscilloscopes
UTD2052CL Digital Storage Oscilloscope
1. Dual analog channels width range 1mV/div~20V/div;
2. 7 inches widescreen LCD displays;
3. Special Print Scree Feature;
4. Supports plug-and-play USB storage device. Communication with and remote control of computer through the USB device;
5. USB drive system software upgrade;
6. Storage of waveforms setups and interfaces waveforms and setups reproduction;
7. Automatic measurement of 28 waveform parameters;
8. Unique waveform recording and replay function;
9. Multilingual menu displays.SKU: n/a -
Environment Meters
UT361 Anemoscopes
UT360 series anemograph is a professional anemograph used to measure wind temperature, wind speed and wind capacity, which is of stable performance, reliable and of neoteric appearance. The device can be widely used in the fields such as environmental protection, labor hygiene, industrial enterprise, scientific research. It is applied to environmental noise measurement, machinery equipment noise and architectural acoustics measurement.
SKU: n/a
There are no reviews yet.