MRU-10 is a simple meter that allows you to measure grounding by the use of the technical method and to measure grounding resistance by the use of the 2-pole method. The instrument is easy to handle, resistive to interference, and highly accurate. MRU-10 is a basic device that allows checking the quality of the grounding system on the basis of the received measurement result. Its ergonomic shape, durable and firm housing, as well as big and clear display make this instrument ideal to use both in the field and most working environments. The device is simple to operate and intuitive. It is the best choice for electrical installations contractors, technicians, and professionals dealing with grounding measurements.
MRU-10 Earth Resistance Meter
3 in stock
It allows to:
- measure earthing resistance using auxiliary electrodes,
- measurement of resistance of auxiliary electrodes RS and RH,
- measurement of interference voltage,
- measurement in the presence of interference voltage in the power network with frequency 50 Hz and 60 Hz,
- selection of maximum measuring voltage (25 V and 50 V),
- indication of battery state.
₨0
3 in stock
CompareWeight | 1 kg |
---|---|
Dimensions | 22 × 10 × 6 cm |
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(10% m.v. + 1 digit) |
Measurement of earthing resistance (method 3-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (for 50 V)
Range | Resolution | Accuracy |
0,00…19,99 Ω | 0,01 Ω | ±(3% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200…1999 Ω | 1 Ω | ±5% m.v. |
2000…9999 Ω | 1 Ω | ±8% m.v. |
- measurement current: under short circuit >20 mA,
- voltage on open terminals: selectable 25 V AC or 50 V AC,
- frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz),
- selection of measuring frequency in settings.
Measurement of earthing resistance (method 2-pole)
Range | Resolution | Accuracy |
0,01…19,99 Ω | 0,01 Ω | ±(3% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | |
200,0…1999 Ω | 1 Ω | ±5% m.v. |
2000…9999 Ω | 1 Ω | ±8% m.v. |
Measurement of earthing resistance (method 2-pole) RH and RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±8% m.v. |
1,00…9,99 kΩ | 0,01 Ω | |
10,0…19,9 kΩ | 0,1 Ω |
Electric security:
- type of insulation: double, according to EN 61010-1 and IEC 61557,
- measurement category: CAT IV 150 V acc. to EN 61010-1,
- protection class acc. to EN 60529: IP67.
Rated operational conditions:
- operation temperature: -10…+50°C,
- storage temperature: -20…+60°C,
- humidity: 20…90%.
Other technical data:
- LCD display: segment, backlit,
- dimensions: 221 x 102 x 62 mm,
- number of measurements (RE3P) carried out of set of batteries: > 3000
Based on 0 reviews
Be the first to review “MRU-10 Earth Resistance Meter”
-
Function Generators
UTG2062B Function/Arbitrary Waveform Generator
1. 1μHz full-band resolution
2. 5MHz~30MHz pulse waveform, adjustable rise/fall time3. 14-bit/16-bit vertical resolution4. Two equivalent-performance channels5. Max arbitrary waveform length of 8k/16M points; 48/1616. non-volatile waveforms storageSKU: n/a -
-
Clamp Meters
UT211B 60A Mini Clamp Meter
UT211B 60A mini clamp meter is a high precision tool designed with the resolution of 0.1mA. UT211B is perfect for anyone requiring high precision and accurate results when working with electronics, such as troubleshooting solar power systems current load, electrical cars, etc. It is ergonomically designed and also lightweight, making it a convenient tool for working in tight spaces.
SKU: n/a -
Environment Meters
UT362 Anemometer
1. Data hold, LCD backlight
2. ℃/℉ selectable3. Auto power off (cancelable)4. 2044 sets data storage5. Auto record function with 0 .5~255s interval6. Wearproof fan shaft for improved accuracy and reliability7. Wind speed modes: MAX, MIN, Real-time8. Wind count modes: MAX, 2/3 MAX, MIN, AVG, real-time9. 7 selectable units: m/s, km/h, ft/min, MPH, KNOTS, CFM, CMMSKU: n/a -
There are no reviews yet.