Earth Resistance Meter
Earth Ground Resistance Testers
MRU-21 Earth Resistance Meter
Availability:
2 in stock
Possible measurements:
- earth resistance measurment with 3-pole method,
- measurement of continuity of equipotential bondings and protective conductors with auto-zero function – with current 200 mA,
- resistance measurement using 2-pole method.
₨0
2 in stock
CompareWeight | 1.4 kg |
---|---|
Dimensions | 29 × 22 × 7 cm |
Measurement of earthing resistance
measurement range to IEC61557 – 5:
0,50 Ω…1,99 kΩ for Un=50 V;
0,68 Ω…1,99 kΩ for Un=25 V;
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…999 Ω | 1 Ω | |
1,00k…1,99 kΩ | 0,01 kΩ |
• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable <25 V AC or <50 V AC,
• frequency of measurement current: 125 Hz
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(2% m.v. + 3 digits) |
• measurement for DC and AC 45…65 Hz
Measurement of resistance of auxiliary electrodes RH i RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±(5% (RS+RE+RH) + 3 digits) |
1,00k…9,99 kΩ | 0,01 kΩ | |
10,0k…50,0 kΩ | 0,1 kΩ |
Measuremet of continuity of equipotential bondings and protective conductors
measurement range to IEC61557 – 4: 0,13 Ω…199 Ω
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…199 Ω | 1 Ω |
- measuring method: technical 2-pole method,
- max. voltage on open terminals: 13 V,
- measurement current: under short circuit >200 mA,
- auto-zero function for measurement leads
Electric security:
- type of insulation: double, according to EN 61010 – 1and IEC 61557
- measurement category: CAT IV 300 V acc. to EN 61010 – 1
- protection class acc. to EN 60529: IP54
Rated operational conditions:
- operation temperature: -10…+55°C
- storage temperature: -20…+70°C
- humidity: 20…80%
Other technical data:
- LCD display: segment, backlit
- interface: USB,
- number of measurements carried out of set of batteries: > 1000 (5 Ω, 2 meas./min.)
- warranty: 2 years
- dimentions: 288 x 223×75 mm
- weigth: 1,4 kg
Based on 0 reviews
Be the first to review “MRU-21 Earth Resistance Meter”
-
LCR Meter
UT622A Digital Inductance LCR Meter
Specifications UT622A UT622C UT622E Certificates CE, RoHS Test frequency 100Hz, 120Hz, 1kHz, 10kHz 100Hz, 120Hz, 1kHz, 10kHz, 100kHz 100Hz, 120Hz, 1kHz, 10kHz, 100kHz Test signal level 0.1Vrms, 0.3Vrms, 1Vrms Output impedance 100Ω Measurement parameters Primary: L/C/R/Z
Secondary: D/Q/θ/ESRPrimary: L/C/R/Z/DCR Secondary: D/Q/θ/ESR Auto LCR √ Test terminals Three-terminal test jacks, five-terminal test sockets Test rate Fast (20 times/s), medium (5 times/s), or slow (2 times/s) DCR test rate — — Fast (20 times/s), medium (5 times/s), or slow (2 times/s) Ranging mode Auto/hold Tolerance range 1%~20% Testing circuit mode Series/parallel mode Clearing correction Open/short circuit Fuse of test ports 0.1A/250V Communication interface Mini-USB LED alarm for tolerance
(pass: green; fail: red)√ √ √ Display range Maximum reading 99999 Minimum resolution 0.0001 Maximum accuracy 0.001 L 0.00μH~99.999H C 0.00pF~99.999mF Z/R 0.0000Ω~9.9999MΩ ESR 0.0000Ω~999.99Ω D 0.0000~9.9999 Q 0.0000~99999 θ -179.9°~179.9° DCR — — 0.01mΩ–20.000MΩ Temperature coefficient 0.1× (specified accuracy) /°C (0°C~18°C or 28°C~40°C) General Characteristics Power 3.7V 1800mAh lithium polymer battery; Input: 220V (1±10%), 50Hz (1±5%); Mini-USB output: 5V, 1A Display 2.8′ TFT LCD 320X240 Product net weight 420g Product size 93mm x 192mm x 44mm Standard accessories Short circuit board (UTR-001), USB cable, 5V 1A power adapter, Four-terminal Kelvin testleads (UTR-L100k-H) (UT622C/E), Alligator clip test leads with rubber plugs (UTR-002)(UT622A), English manual SKU: n/a