MIC-15k1 ,15kV Insulation Quality Analyzer

Availability:

1 in stock


 

Features:

  • Diagnostics of insulation systems based on standard measurements of IR, DAR, PI, SV, RT, DD, widened with thepartial discharge (PD) indicator for every each of these measurements.
  • It allows testing the electrical durability of the tested object – breakdown voltage indication.
  • High resistance to electromagnetic interferences guarantees uninterrupted work in power stations and close to high voltage transmission lines up to 1200 kV AC and 500 kV DC.
  • The function of smooth voltage rise in time (RT – Ramp Test) allows to state the partial discharges in the facility and to carry out a partial location of their occurrence.
  • Efficient converter with a power of ~150 W that enables insulation burnout, allowing for pinpointing the location of cables and wires short circuit using one of the following:
    • visual method (if power cables are visible along the entire length),
    • reflectometric methods, seismic-acoustic waves detector, or with A-frame to indicate direction of the fault (the conductor must be buried in the ground with earth direct contact).
  • Compatible with external software.

0

1 in stock

Compare

MIC-15k1 meter is designed to measure insulation resistance of power objects, i.e.:

  • single- and multicore cables,
  • transformers,
  • motors and generators,
  • capacitors, switches and other devices installed in power stations.

It is especially recommended for measurements in areas with very high electromagnetic disturbances, e.g. electrical substations with 1200 kV AC and 500 kV DC. Thanks to the 15 kV measuring voltage (in accordance with ANSI / NETA ATS-2009 TABLES 100.1) the meter can be used for measuring objects with a nominal voltage above 34.5 kV.

Category:
Weight 6.3 kg
Dimensions 39 × 31 × 17 cm

Insulation resistance measurement
Measuring range according to IEC 61557-2
UN = 15 000 V: 50 kΩ…40.0 TΩ
Measurement with DC and increasing voltage (SV) for UISO = 15 kV

Range Resolution Accuracy
0,0…999 kΩ 1 kΩ ±(3% m.v. + 10 digits)
1,00…9,99 MΩ 0,01 MΩ ±(3% m.v. + 10 digits)
10,0…99,9 MΩ 0,1 MΩ ±(3% m.v. + 10 digits)
100…999 MΩ 1 MΩ ±(3% m.v. + 10 digits)
1,00…9,99 GΩ 0,01 GΩ ±(3% m.v. + 10 digits)
10,0…99,9 GΩ 0,1 GΩ ±(3% m.v. + 10 digits)
100…999 GΩ 1 GΩ ±(3,5% m.v. + 10 digits)
1,00…9,99 TΩ 0,01 TΩ ±(7,5% m.v. + 10 digits)
10,0…20,0 TΩ 0,1 TΩ ±(12,5% m.v. + 10 digits)
10,0…40,0 TΩ 0,1 TΩ ±(12,5% m.v. + 10 digits)

Ranges of measured resistance depending on the test voltage

Voltage UISO Measuring range
50 V 200 GΩ
100 V 400 GΩ
250 V 1,00 TΩ
500 V 2,00 TΩ
1000 V 4,00 TΩ
2500 V 10,00 TΩ
5000 V 20,0 TΩ
10 000 V 40,0 TΩ
15 000 V 40,0 TΩ

Capacitance measurement

Range Resolution Accuracy
0…999 nF 1 nF ±(5% m.v. + 5 digits)
1,00…49,99 µF 0,01 µF ±(5% m.v. + 5 digits)
  • Displaying measured capacity after RISO measurement
  • For measurement voltages below 100 V the measurement error is not specified

Technical specification

  • type of insulation acc. to: EN 61010-1 and IEC 61557 double
  • measurement category acc. to EN 61010-1
    • IV 1000 V (operating altitude ≤2000 m)
    • IV 600 V (operating altitude ≤3000 m)
  • ingress protection acc. to EN 60529: IP67 (IP40 for closed case)
  • resistance to external interference voltages: up to 1550 V
  • resistance to external interference currents: up to 10 mA
  • advanced, digital filtering of interferences: 10 / 30 / 60 / 100 / 200 seconds
  • test leads lock: yes
  • power supply: Li-Ion 14.8 V rechargeable battery from network 90 V ÷ 260 V, 50 Hz/60 Hz
  • dimensions: 390 x 308 x 172 mm
  • weight: approx. 6.3 kg
  • storage temperature: -25ºC…+70ºC
  • operating temperature: -20ºC…+50ºC
  • humidity: 20%…90%
  • operating altitude: ≤3000 m
  • reference temperature: +23ºC ± 2ºC
  • reference humidity: 40%…60%
  • display: graphical LCD
  • number of RISO measurements with battery power supply: min. 1000 acc. to EN 61557-2
  • data transmission: USB and Bluetooth
  • quality standard: ISO 9001 compliant
  • device meets the requirements of standards: EN 61010-1 and IEC 61557
  • the product meets EMC requirements (immunity for industrial environment) with accordance to standards: EN 61326-1 and EN 61326-2-2

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MIC-15k1 ,15kV Insulation Quality Analyzer”

There are no reviews yet.

  • SOLDERING IRON WOOD 75W BLUE

    0 out of 5
    (0)

    SOLDERING IRON WOOD 75W BLUE

    SKU: n/a
  • YIHUA 3010D DC Power supply

    0 out of 5
    (0)

    This model has compact design with all metal construction.

    1.This unit now features a Dual LED display with highly accurate LED digital readout.

    2.Maximum output is 30V at 10A.

    1. High stabilized output voltage.
    2. Short circuit protection.

    5.Over loading and current protection.

    SKU: n/a
  • UT-L21 Probe UT-L Probes and Test Leads

    0 out of 5
    (0)

    Leads length: 900mm

    Rod length: 133mm
    Tip length: 15.8mm
    Safety level: CAT Ⅲ 1000V/CAT Ⅳ 600V 20A
    Features and application: cross plug with shield sleeve, general type probe
    Amount: 1PCS

    SKU: n/a
  • MECHANIC Industrial Triocular stereo microscope MC75T-B3

    0 out of 5
    (0)

    Binocluar magnification(7X-45X/2.1X-180X)

    Eyepiece(WF10X/20MM,WF20X/10MM)

    Objectlens(10.6X-5.5X),

    Aux(0.3X/287,0.5X/165,0.7X/120,1.5X/45,2X/30)

    Continuourszoom(0.7X-4.5X)

    SKU: n/a
  • The Sanwa CD800a is a basic, portable, 4000 count digital multimeter

    0 out of 5
    (0)
    • 4000 counts
    • 0.7% Best Accuracy
    • Sharp contrast LCD with character 17.5mm high is used
    • Solid & protective body cover that can also be used as a tilt stand
    • Frequency, capacitance, and duty cycle measurement function
    • Continuity test with buzzer

    Includes meter, instruction manual and test leads.

    SKU: n/a