Earth Resistance Meter
MRU-21 Earth Resistance Meter
2 in stock
Possible measurements:
- earth resistance measurment with 3-pole method,
- measurement of continuity of equipotential bondings and protective conductors with auto-zero function – with current 200 mA,
- resistance measurement using 2-pole method.
₨0
2 in stock
CompareWeight | 1.4 kg |
---|---|
Dimensions | 29 × 22 × 7 cm |
Measurement of earthing resistance
measurement range to IEC61557 – 5:
0,50 Ω…1,99 kΩ for Un=50 V;
0,68 Ω…1,99 kΩ for Un=25 V;
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…999 Ω | 1 Ω | |
1,00k…1,99 kΩ | 0,01 kΩ |
• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable <25 V AC or <50 V AC,
• frequency of measurement current: 125 Hz
Measurement of interference voltage UN (RMS)
Range | Resolution | Accuracy |
0…100 V | 1 V | ±(2% m.v. + 3 digits) |
• measurement for DC and AC 45…65 Hz
Measurement of resistance of auxiliary electrodes RH i RS
Range | Resolution | Accuracy |
0…999 Ω | 1 Ω | ±(5% (RS+RE+RH) + 3 digits) |
1,00k…9,99 kΩ | 0,01 kΩ | |
10,0k…50,0 kΩ | 0,1 kΩ |
Measuremet of continuity of equipotential bondings and protective conductors
measurement range to IEC61557 – 4: 0,13 Ω…199 Ω
Range | Resolution | Accuracy |
0,00…9,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
10,0…99,9 Ω | 0,1 Ω | |
100…199 Ω | 1 Ω |
- measuring method: technical 2-pole method,
- max. voltage on open terminals: 13 V,
- measurement current: under short circuit >200 mA,
- auto-zero function for measurement leads
Electric security:
- type of insulation: double, according to EN 61010 – 1and IEC 61557
- measurement category: CAT IV 300 V acc. to EN 61010 – 1
- protection class acc. to EN 60529: IP54
Rated operational conditions:
- operation temperature: -10…+55°C
- storage temperature: -20…+70°C
- humidity: 20…80%
Other technical data:
- LCD display: segment, backlit
- interface: USB,
- number of measurements carried out of set of batteries: > 1000 (5 Ω, 2 meas./min.)
- warranty: 2 years
- dimentions: 288 x 223×75 mm
- weigth: 1,4 kg
Based on 0 reviews
Be the first to review “MRU-21 Earth Resistance Meter”
-
Environment Meters
UT361 Anemoscopes
UT360 series anemograph is a professional anemograph used to measure wind temperature, wind speed and wind capacity, which is of stable performance, reliable and of neoteric appearance. The device can be widely used in the fields such as environmental protection, labor hygiene, industrial enterprise, scientific research. It is applied to environmental noise measurement, machinery equipment noise and architectural acoustics measurement.
SKU: n/a -
Wire & Cable Testers
UT681HDMI Cable Tester
1. Tests HDMI/MINI-HDMI cables
2. Fastline collocation type: A with A, A with C and C with C
3. Checks circuit breakage, short circuit, cross circuit and the missing wire
4. 20 visible LED indicators
5. Can toggle between scan and full display test modes
6. Single key operation
7. Manual/auto power off (after 10-minute inactivity)
8. Low battery indication
9. CE certification
10. Power supplied by 9V layer-built battery
SKU: n/a -
Clamp Meters
UT281C True RMS AC 3000A Flexible Clamp Meters
1. 2m drop proof, IP54, ETL/Intertek certified 3rdedition CE
2. Coil diameter: 0.75cm, bending length: 24.5cm for UT281A and 45.7cm for UT281C
3. Large LCD display for clear reading
4. True RMS
5. Long press INRUSH key for 2s to measure inrush current
6. Datahold, backlight, auto power off
SKU: n/a
There are no reviews yet.