PQM-707 Power Quality Analyzer


  • Features:

    • 7″ touch screen – intuitive operating
    • CAT IV 600V – high safety
    • all parameters acc. to class S – high accuracy of measurements
    • Li-Ion rechargeable battery – higher mobility
    • removable memory card – recording data with no restrictions

    Possible measurements:

    • Measurements according to EN 50160,
    • Voltage L1, L2, L3, N-PE (five inputs),
      – average, minimum, maximum values, range to 760 V, ability to work with voltage transformers,
    • Current L1, L2, L3, N (four inputs),
      – average, minimum, maximum values, measurement current with range to 3 kA (depends on used clamp), ability to work with current transformers,
    • Crest factor for voltage and current,
    • Frequency from 40 Hz to 70 Hz ,
    • Active, reactive, distortion, apparent power, including the type of reactive power (capacitive, inductive),
    • Power recording:
      • Budeanu method,
      • IEEE 1459,
    • Active, reactive, apparent energy,
    • Power factor, cosφ, tgφ,
    • Up to 50th harmonics for voltage and current,
    • Total Harmonic Distortion (THD) for voltage and current,
    • Short-term (PST) and long-term (PLT) flicker,
    • Unbalance of voltage and current,
    • Current and voltage events registration including waveforms and RMS graphs half period,
    • Inrush current
    • Calculator of energy tariffs
    • ANALYZER MEASURES AND RECORDS ACCORDING TO THE IEC 61000-4-30 CLASS S STANDARD.

0

Compare

Power Quality Analyzer Sonel PQM-707 is an autonomous meter allowing for versatile measurement, analysis, and registration of energy networks parameters DC and 50/60Hz, including the quality of electric energy in accordance with the European standard EN 50160 and the Regulation of the Minister of Economy on detailed conditions of the  electro-energetic system functioning. All parameters are measured in the S class of the IEC 61000-4-30 STANDARD guaranteeing high accuracy of measurements.
The largest in this class of analyzers 7-inch colour touch screen enables intuitive and ergonomic operation. Thanks to the built-in lithium-ion battery, the analyzer allows for efficient work during the measurement without the necessity of connecting an external AC adapter.

The analyzer is directed to a very wide range of users, with particular reference to the maintenance staff. Due to its mobility and autonomy, any problems occurring in the supply networks can be diagnosed on the spot. High measurement category (CAT IV 600V) makes the analyzer very safe, which provides peace of mind during every day use.
The analyzer can be used in virtually all kinds of networks with rated voltage from 54V to 760V directly, or indirectly via transformers.
Because of that PQM-707 can be used in the field of professional power engineering, maintenance services in industrial plants, as well as among those providing services focused on network analysis.

Accessories:

  • Test leads 2.2 m
  • Mains cable with IEC C7 plug
  • Crocodile clips, black,yellow,red,blue.
  • Power supply adaptor Z7
  • USB Transmission Cable
  • Carrying Case
  • F-3A flexible clamps (Φ=120 mm)
  • AC-16 line Splitter
  • AZ-2 Power Supply Adaptor
  • Cable for Battery
  • Magnetic voltage adapter (set – 4 pcs)

The device is designed to work with networks:

  • with nominal frequency 50/60 Hz,
  • with nominal voltage: 64/110 V; 110/190 V; 115/200 V; 127/220 V; 220/380 V; 230/400 V; 240/415 V; 254/440 V; 290/500 V; 400/690 V.
  • DC network

Supported networks:

  • single-phase,
  • two-phase with common N conductor,
  • three-phase star connection with and without N conductor,
  • three-phase delta.
  • Parameters of analyzer:

    Parametr Parametr Measurement range Max. resolution Accuracy
    Alternating voltage (TRMS) 0,0…760,0 V 0,01 % Unom ±0,5% Unom
    Crest Factor Voltage 1,00…10,00 (≤1.65 for 690 V voltage) 0,01 ±5%
    Crest Factor Current 1,00…10,00 (≤3,6 Inom) 0,01 ± 5%wm
    Alternating current TRMS depending on clamp* 0,01 % Inom ±2% m.v. for m.v. ≥ 10% Inom ±2% Inom for m.v. < 10% Inom(error does not account for clamps error)
    Frequency 40,00…70,00 Hz 0,01 Hz ±0,05 Hz
    Active, reactive, apparent and distortion power depending of configuration (trasformers, clamp) up to for decimal places depending on configuration (transformers, clamps)
    Active, reactive apparent energy depending of configuration (transformers, clamp) up to for decimal places as power error
    cosφ and power factor (PF) 0,00…1,00 0,01 ±0,03
    Tgφ 0,00…10,00 0,01 depends on active and reactive power error
    Harmonics Voltage as for alternating voltage True RMS as for alternating voltage True RMS ±5% m.v. for m.v. ≥ 3% Unom ±0,15% Unom for m.v.. < 3% Unom
    Harmonics Current as for alternating voltage True RMS as for alternating voltage True RMS ±5% m.v. for m.v.. ≥ 10% Inom ±0,5% Inom for m.v. < 10% Inom
    THD Voltage 0.0..100.0% (in regards to the rms value) 0,1% ±5%
    THD Current 0.0..100.0% (in regards to the rms value) 0,1% ±5%
    Flicker severity PST, PLT 0,40…10,00 0,01 ±10%
    Voltage asymmetry Voltage and current 0,0…10,0% 0,1% ±0,15% (absolute error)
    Inrush current depending on clamp* 0,01% Inom ±4% m.v. for m.v. ≥ 10% Inom ±4% Inom for m.v. < 10% Inom(RMS1/2)

    *Clamp F-1A, F-2A, F-3A: 0..3000 A (10000 Ap-p)

    *Clamp C-4A: 0..1000 A (3600 Ap-p)

    *Clamp C-5A: 0..1000 A (3600 Ap-p)

    *Clamp C-6A: 0..10 A (36 Ap-p)

    *Clamp C-7A: 0…100 A (360 Ap-p)

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “PQM-707 Power Quality Analyzer”

There are no reviews yet.

  • UT230B-EU Power Socket

    0 out of 5
    (0)
    SKU: n/a
  • JM-8146 47 in 1 Household Maintenance Tool

    0 out of 5
    (0)

    Multi-function Tools

    SKU: n/a
  • UT622A Digital Inductance LCR Meter

    0 out of 5
    (0)
    Specifications UT622A UT622C UT622E
    Certificates CE, RoHS
    Test frequency 100Hz, 120Hz, 1kHz, 10kHz 100Hz, 120Hz, 1kHz, 10kHz, 100kHz 100Hz, 120Hz, 1kHz, 10kHz, 100kHz
    Test signal level  0.1Vrms, 0.3Vrms, 1Vrms
    Output impedance 100Ω
    Measurement parameters Primary: L/C/R/Z
    Secondary: D/Q/θ/ESR
    Primary: L/C/R/Z/DCR  Secondary: D/Q/θ/ESR
    Auto LCR
    Test terminals Three-terminal test jacks, five-terminal test sockets
    Test rate Fast (20 times/s), medium (5 times/s), or slow (2 times/s)
    DCR test rate Fast (20 times/s), medium (5 times/s), or slow (2 times/s)
    Ranging mode Auto/hold
    Tolerance range 1%~20%
    Testing circuit mode Series/parallel mode
    Clearing correction Open/short circuit
    Fuse of test ports 0.1A/250V
    Communication interface Mini-USB
    LED alarm for tolerance
    (pass: green; fail: red)
    Display range
    Maximum reading 99999
    Minimum resolution 0.0001
    Maximum accuracy 0.001
    L 0.00μH~99.999H
    C 0.00pF~99.999mF
    Z/R 0.0000Ω~9.9999MΩ
    ESR 0.0000Ω~999.99Ω
    D 0.0000~9.9999
    Q 0.0000~99999
    θ -179.9°~179.9°
    DCR 0.01mΩ–20.000MΩ
    Temperature coefficient 0.1× (specified accuracy) /°C (0°C~18°C or 28°C~40°C)
    General Characteristics
    Power 3.7V 1800mAh lithium polymer battery; Input: 220V (1±10%), 50Hz (1±5%); Mini-USB output: 5V, 1A
    Display 2.8′ TFT LCD 320X240
    Product net weight 420g
    Product size 93mm x 192mm x 44mm
    Standard accessories Short circuit board (UTR-001), USB cable, 5V 1A power adapter, Four-terminal Kelvin testleads (UTR-L100k-H) (UT622C/E), Alligator clip test leads with rubber plugs (UTR-002)(UT622A), English manual
    SKU: n/a
  • JAKEMY JM-CT4-3 crimping plier crimping diy repair hand tool

    0 out of 5
    (0)

    JAKEMY JM-CT4-3 Network 4P 6P 8P crimping plier crimping diy repair hand tool

    SKU: n/a
  • UT256A

    0 out of 5
    (0)

    UT256 series are high reliable, true RMS fork meters. Its unique design allows users to measure current by simply moving the wire ofinterest inside the opening of the ‘fork’ past the labeled mark. With no mechanical parts, this meter bares no risk from any type ofmechanical failure.

    SKU: n/a