UT270 series can measure the grounding system of a circuit without disconnecting the ground wires and auxiliary electrode. It clamps the grounding circuit and measures the grounding resistance fast and safely. It can measure resistance as low as 0.01Ω and has a high resolution of 0.001Ω. It has overload alarm function, which can help to setup the alarm value within the ranges. The clamp has double insulation, which strengthens the anti-interference.
UT275 Clamp Earth Ground Testers
Out of stock
UT270 series can measure the grounding system of a circuit without disconnecting the ground wires and auxiliary electrode. It clamps the grounding circuit and measures the grounding resistance fast and safely. It can measure resistance as low as 0.01Ω and has a high resolution of 0.001Ω. It has overload alarm function, which can help to setup the alarm value within the ranges. The clamp has double insulation, which strengthens the anti-interference.
₨94,800 ₨96,000
Out of stock
CompareWeight | 1.3 kg |
---|---|
Dimensions | 29 × 9 × 7 cm |
Specifications | Range | Best Accuracy |
Model | UT275 | |
Earth Ground Resistance (Ω) | 0.01~0.099Ω | ±(1%+0.01) |
0.1~0.99Ω | ±(1%+0.01) | |
1.0~49.9Ω | ±(1.5%+0.1) | |
50.0~99.5Ω | ±(2%+0.5) | |
100~199Ω | ±(3%+1) | |
200~395Ω | ±(10%+5) | |
400~590Ω | ±(20%+10) | |
600~1000Ω | ±(25%+20) | |
Leakage Current(A) | 0.00~299mA | ±(2.5%+2mA) |
0.30~2.99A | ±(2.5%+100mA) | |
3.00~30.0A | ±(2.5%+300mA) | |
Features | ||
Display Count | 9999 | |
Auto Range | √ | |
Jaw Capacity | 28mm | |
Auto Power Off | √ | |
Low Battery Indication | ≤5.2V | √ |
Data Hold | √ | |
Data Logging | 30 | |
Data Recall | √ | |
LCD Backlight | √ | |
Auto Calibration | √ | |
Resistance Limit Alarm | √ | |
General Characteristic | ||
Power | 1.5V Alkaline Batteries(LR6)×4 | |
LCD Size | 47mm X 28.5 mm | |
Product Color | Red and Grey | |
Product Net Weight | 1320g | |
Product Size | 293mm X 90mm X66 mm | |
Standard Accessories | Batteries, Test Ring, Tool Box | |
Standard Individual Packing | Gift Box, English Manual | |
Standard Quantity Per Carton | 5 PCs | |
Standard Carton Measurement | 495mm X 368mm X 310mm (0.057CBM Per Standard Carton) | |
Standard Carton Gross Weight | 16Kg |
Based on 0 reviews
Be the first to review “UT275 Clamp Earth Ground Testers”
-
Insulation Tester
MIC-5001, 5000V Insulation Tester
Insulation resistance measurement in a compact, light-weight, low-cost design.
- Measurement to 5 TΩ
- Measuring voltage selectable from 50 V to 500 V range in 50 V steps, and from 500 V to 5000 V range in 100 V steps
- Continuous indication of insulation resistance or leakage current
- Automatic discharge of stored charge due to capacitance of tested object after the insulation resistance measurement
- Audio beeps every five seconds to alert user test is proceeding, and to get time characteristics
- Measured test times of T1, T2 and T3 for measuring Absorption Coefficient, Dielectric Absorption Ratio DAR. and Polarization Index PI
- Continuous display of test voltage during the measurement
- Protection against measuring live objects
- Two and three-lead measurement method
- Ramp Test Insulation resistance measurement
- Measurement of breakdown voltage with increments up to 1 kV / s
- Measurement of alternating and direct voltages from 0 V to 750 V
- 990 cells of memory (11880 records) to record results
- Data transfer to PC via USB cable
- Built-in rechargeable battery pack
- Meets the requirements of the EN 61557 standard
- Charge from optional car lighter (12 V) socket accessory
SKU: n/a -
Clamp Meters
AC DIGITAL CLAMP METER KEW 2117R
AC DIGITAL CLAMP METER KEW 2117R
• Fully Safety jaw
• Ergonomic over-molded body gives convenient one-hand operation
• Large easy-to-read display with 0.01A resolution
• Accurate reading with True RMS
60/600/1000A auto-ranging
• Long battery life
• Safety Standard
IEC 61010-1 CAT IV 300V / CAT III 600VSKU: n/a -
Oscilloscopes
UNI-T MSO3152E 150MHz Mixed Signal 2 Channel Digital Oscilloscope
Analog bandwidth 150MHz 250MHz Channels 2+16 digital 4+16 digital 2+16 digital 4+ 16digital Sampling rate (Analog) 2.5GS/s (Single channel), 1.25GS/s (Dual channels) Sampling rate (Digital) 1.25GS/s (Eight channels), 625MS/s(Sixteen channels) Memory depth 70Mpts Waveform capture rate 200,000wfms/s Time base scale 2ns/div~50s/div (Real-time sampling rate, memory depth display ) Time base scale (digital) 2ns/div~40S/div[Step by 1-2-4 stall] Input impedance (1MΩ±1%) II (20pF±3pF) Input impedance digital (101kΩ±1%) II (9pF±1pF) Vertical scale 1mV/div~20 V/div (1 MΩ) DC gain accuracy <5mV: ±3%, ≥5mV: ±2% Waveform record 100,000 frames Trigger types Edge, Runt, Window, Nth Edge, Delay, Overtime, Duration, Setup/Hold, Pulse Width, Slop, Video, Code; RS232/UART, I2C, SPI, USB,
CAN, LIN, FlexRayBus decode RS232/UART, I2C, SPI, USB, CAN, LIN, FlexRay Waveform operations A+B, A-B, A×B, A/B, FFT, editable advanced and logical operations Auto measurements
Max, Min, High, Low, Ampl, Pk-Pk, Middle, Mean, CycMean, RMS, CycRMS, Period, Freq, Rise, Fall, RiseDelay, FallDelay, +Width,
-Width, FRR, FRF, FFR, FFF, LRF, LRR, LFR, LFF, +Duty, -Duty, Area, CycArea, OverSht, PreSht, Phase, 34 parameters in totaldigital
channel: Freq, Period, +Width, -Width, +Duty, -Duty, RiseDelay A→B,FallDelay A→B, Phase A→B, Phase B→AMeasurement display 5 types Measurement statistics Average, Max, Min, standard deviation and number of measurements Frequency counter 6 bits Standard interfaces USB Host, USB Device, LAN, EXT Trig, AUX Out (Trig Out, Pass/Fail), AWG,UT-M15 logic analyzer probe, VGA Standard Accessories
USB interface cable UT-D14 Passive Probe x 2/4 (1 x , 10 x switchable,300MHz,) UT-P06 Passive Probe x 2/4 (1 x , 10 x switchable,200MHz,) UT-P05 16CH Logic analyzer probe UT-15M SKU: n/a
There are no reviews yet.