UT270 series is widely used in earth ground and circuit resistance measurements of electric power, telecommunications, meteorology, oil field, construction and industrial electrical equipment. It can measure the ground system of the circuit without disconnecting grounding wires, auxiliary electrode. UT278A can also measure leakage current and neutralline current of earth ground system.
UT278A Clamp Earth Ground Testers
Out of stock
UT270 series is widely used in earth ground and circuit resistance measurements of electric power, telecommunications, meteorology, oil field, construction and industrial electrical equipment. It can measure the ground system of the circuit without disconnecting grounding wires, auxiliary electrode. UT278A can also measure leakage current and neutralline current of earth ground system
.
₨0
Out of stock
CompareWeight | 1.1 kg |
---|---|
Dimensions | 28 × 8 × 6 cm |
Specifications | Range | Best Accuracy |
Model | UT278A | |
Earth Ground Resistance (Ω) | 0.01Ω-0.099Ω | ±(1%+0.01) |
0.1Ω-0.99Ω | ±(1%+0.01) | |
1.0Ω-49.9Ω | ±(1%+0.1) | |
50Ω-99.5Ω | ±(2%+0.5) | |
100Ω-199Ω | ±(3%+1) | |
200Ω-395Ω | ±(6%+5) | |
400Ω-590Ω | ±(10%+10) | |
600Ω-800Ω | ±(20%+20) | |
800Ω-1200Ω | ±(25%+30) | |
Leakage Current(A) | 0mA-9mA | ±(2.5%+1) |
10mA-99mA | ±(2.5%+5) | |
100mA-299mA | ±(2.5%+10) | |
0.30A-2.99A | ±(2.5%+0.1) | |
3.0A-9.9A | ±(2.5%+0.3) | |
10.0A-20.0A | ±(2.5%+0.5) | |
3A-30A | ±(2.5%+0.5) | |
Features | ||
Display Count | 4 Digits Display LCD | √ |
Auto Range | √ | |
Jaw Capacity | 32mm | |
Single Measure Time | 1 Second | √ |
Resistance Measurement Frequency | >1KHz | √ |
Current Measurement Frequency | 50Hz/60Hz | √ |
Resistance Limit Alarm | 1Ω-199Ω | √ |
Current Limit Alarm | 1mA-499mA | √ |
Beeper and Light Alarm | √ | |
Jamming Signal Recognition | √ | |
Over-Range Display | √ | |
Low Battery Indication | √ | |
Data Logging | 99 | |
General Characteristic | ||
Power | 1.5V Alkaline Batteries(LR6)X 4 | |
LCD Size | 47mm X 28.5mm | |
Product Color | Red and Grey | |
Product Net Weight | 1160g | |
Product Size | 285mm X 85mm X 56mm | |
Standard Accessories | Batteries, Test Ring, Tool Box | |
Standard Individual Packing | Gift Box, English Manual | |
Standard Quantity Per Carton | 6 PCs | |
Standard Carton Measurement | 610mm X 375mm X 320mm (0.073CBM Per Standard Carton) | |
Standard Carton Gross Weight | 25Kg | |
Optional Accessories | USB Interface Cable,PC Software CD |
Based on 0 reviews
Be the first to review “UT278A Clamp Earth Ground Testers”
-
Digital Multi Meter
ET 8133 DMM
Product description
3 times/second
Diode: YES
Capacitance: YES
True RMS: YES
Data hold: YES
Backlight: YES
Flashlight: YES
Auto power off: YES (no measurement operation within 15 minutes)
Low battery indication: YES
Environment temperature: 0~40℃, humidity <75%
Storage environment: -20~60℃, humidity <80%
DC voltage:
Range: 200mV/2.000V/20.00V/200.0V/600V
Resolution: 0.0001V/0.001V/0.01V/0.1V/1V
Accuracy: ±(0.5%+3)
Max.: 600V
AC voltage:
Range: 2.000V/20.00V/200.0V/600V
Resolution: 0.001V/0.01V/0.1V/1V
Accuracy: ±(1.0%+3)
Max.: 600V
Capacitance:
Range: 20.00nF/200.0nF/2.000F/200.0F
Resolution: 0.01nF/0.1nF/10nF/100nF
Accuracy: ±5%+3
Max.: 200μF
AC current:
Range: 20mA/200mA, 2A, 10A
Resolution: 0.1mA/0.001A/0.01A
Accuracy:
20mA/200mA/2A: ±(1.0%+3)
10A: ±(1.5%+3)
Max.:
20mA/200mA: 200mA
2A/10A: 10A
DC current:
Range: 20mA/200mA, 2A, 10A
Resolution: 0.1mA/0.001A/0.01A
Accuracy:
20mA/200mA: ±(2.0%+4)
2A: ±(1.0%+5)
10A: ±(2.0%+3)
Max.:
20mA/200mA: 200mA
2A/10A: 10A
Resistance:
Range: 2.000KΩ/20.00KΩ/200.0KΩ/2.000MΩ/20.00MΩ
Resolution: 0.001KΩ/0.01KΩ/0.1KΩ/0.001MΩ/0.01MΩ
Accuracy:
2.000KΩ: ±(1.5%+3)
20.00KΩ: ±(0.5%+3)
200.0KΩ: ±(0.5%+3)
2.000MΩ: ±(1.0%+3)
20.00MΩ: ±(1.5%+3)
Max.: 20MΩ
Continuity: YES
NCV: YES
Frequency response in AC mode: 40Hz~1KHz
LCD size: 45 * 25mm / 1.8 * 1.0in
Item size: 124 * 65 * 26mm / 4.9 * 2.6 * 1.0in
Item weight: 210g / 7.4ounce
Package size: 140 * 100 * 40mm / 5.5 * 3.9 * 1.6in