- Insulation resistance measurement:
- selectable measurement voltage in the 100…2500 V range with 100 V step,
- continuous indication of insulation resistance or leakage current,
- automatic discharge of capacitance of tested object after the insulation resistance measurement,
- acoustic signalling of five-second periods to facilitate obtaining time characteristics,
- measured test times T1, T2 i T3 to measure one or two absorption coefficients in 15, 60 and 600 s,
- indication of actual test voltage during the measurement,
- protection against measuring live objects,
- two and three-lead measurement method,
- Continuity measurement of protective and equipotential conductors according to EN 61557-4
- with the >200 mA current.
- Leakage current measurement.
- Measurement of alternating and direct voltages in the 0…750 V range.
- Built-in rechargeable battery pack.
- The instruments meet the requirements of the EN 61557 standard.
- The ability to charge from car lighter (12 V) socket (additional accessories).
MIC-2501,2500V Insulation Resistance Meter
1 in stock
Electrical safety:
- type of insulation: double, in acc. with EN 61010-1 und IEC 61557
- measurement category: IV 600 V (III 1000 V) in acc. to EN 61010-1
- case protection rating in acc. with EN 60529: IP65
Other technical specifications:
- power supply of the meter SONEL L-1 NiMH 9,6 V; DC 12 V 2,5 A
- weight of the meter: approx. 0,9 kg
- dimensions: 200 x 180 x 77 mm
- display: LCD segment display
- measurement results memory: 990 cells, 11880 records,
- transmission of measurement results: USB
₨0
1 in stock
CompareWeight | 0.9 kg |
---|---|
Dimensions | 20 × 18 × 8 cm |
Insulation resistance measurement (two-lead)
Measurement range acc. to IEC 61557-2 for RISOmin=UISOnom/IISOmax…1 TΩ (IISOmax=1 mA)
Range | Resolution | Accuracy |
---|---|---|
0,0…999,9 kΩ | 0,1 kΩ | ±(3% m.v. + 20 digits) |
1,000…9,999 MΩ | 0,001 MΩ | ±(3% m.v. + 20 digits) |
10,00…99,99 MΩ | 0,01 MΩ | ±(3% m.v. + 20 digits) |
100,0…999,9 MΩ | 0,1 MΩ | ±(3% m.v. + 20 digits) |
1,000…9,999 GΩ | 0,001 GΩ | ±(3% m.v. + 20 digits) |
10,00…99,99 GΩ | 0,01 GΩ | ±(3% m.v. + 20 digits) |
100,0…999,9 GΩ | 0,1 GΩ | ±(3% m.v. + 20 digits) |
Values of measured resistance depending on measurement voltage
Voltage UISO | Measurement range |
---|---|
100 V | 50 GΩ |
200…400 V | 100 GΩ |
500…900 V | 250 GΩ |
1000…2400 V | 500 GΩ |
2500 V | 1000 GΩ |
Continuity measurement of protective connections and equipotential bonding with 200 mA current.
Measurement range acc. to EN 61557-4: 0,10…999 Ω
Range | Resolution | Accuracy |
---|---|---|
0,00…19,99 Ω | 0,01 Ω | ±(2% m.v. + 3 digits) |
20,0…199,9 Ω | 0,1 Ω | ±(2% m.v. + 3 digits) |
200…999 Ω | 1 Ω | ±(4% m.v. + 3 digits) |
- Voltage on open terminals: 4…24 V
- Output current at R <2 Ω: ISC >200 mA
- Compensation of test lead resistance
- Current flowing in both directions, mean value of resistance is displayed
DC and AC voltage measurement
Range | Resolution | Accuracy |
---|---|---|
0…299,9 V | 0,1 V | ±(3% m.v. + 2 digits) |
300…750 V | 1 V | ±(3% m.v. + 2 digits) |
- Frequency range: 45…65 Hz
The acronym “m.v.” stands for a “measured reference value”.
Based on 0 reviews
Be the first to review “MIC-2501,2500V Insulation Resistance Meter”
-
Soldering Iron
Mechanic Special Solder Paste XG-50 35G 183°C
This is solder paste for soldering small SMD components in a reflow oven or with a hot air soldering station. comes in a small container for prototyping or repairing job.This pack is the right amount of solder paste for most hobby projects. This paste is the replacement for solder wire used in Through-hole soldering, some times solder flux is referred to as solder paste.
SKU: n/a -
Phase Detector Meters
TKF-12 Phase Sequence Tester
Phase sequence indication (direction of field rotation) in the power network with rated phase-to-phase voltage (120…690 V) AC by LED signalization.
Operation in the power network with frequency range 10…70 Hz.
Indication of the voltage presence in the particular phases by neon lamps signalization.
Power supply from the tested network (continuous operation to 15 minutes for max. voltage).
Protection against faulty indication of field rotation.SKU: n/a -
Clamp Meters
UT207A Digital Clamp Meters (Discontinued)
Features of UT207/A to UT209/A Series 1000A Digital Clamp Meters
Certificates: CE, RoHS
● 1000A AC/DC current measurement, 3 times/s sampling rate
● Auto/manual ranges selectable (UT207A/UT208A/UT209A)
● True RMS (UT207/UT208/UT209/UT209A)
● Analog bar graph (UT209)
● Inrush current (UT207/UT208)
● Zeroing function
● Full icon display (UT207/UT208/UT209)
● MAX/MIN (UT207/UT208/UT209)
● LCD backlight (UT207A/UT208A/UT209A)
● Data hold; Duty cycle (except UT209 )
● Auto power off and low battery indication
● Point contact temperature probe (UT208/UT208A)
● Diode; Continuity buzzer; Input Impedance for DCVSKU: n/a
There are no reviews yet.