MRU-30 Earth Resistance and Resistivity Meter

Availability:

3 in stock


 

  • It allows to take the measurements of:

    • earthing resistance using auxiliary electrodes,
    • earthing resistance using auxiliary electrodes and clamp (for measurements of multiple earthing),
    • earthing resistance using double clamps for measuring multiple earthing without underground connections.
    • ground resistivity (Wenner method),
    • continuity of equipotential bondings and protective
    • conductors (meeting the requirements IEC 60364) with auto-zero function – with current 200mA.

    Additionally:

    • measurement of resistance of auxiliary electrodes RS and RH,
    • measurement of interference voltage,
    • measurement in the presence of interference voltage in the power network
    • with frequency 50Hz, 60Hz,
    • selection of maximum measuring voltage (25V and 50V),
    • introducing the distance between the electrodes for the resistivity in metres (m) and feet (ft),
    • memory of 990 measurements (10 banks of 99 cells each),
    • calibration of clamp used,
    • data transmission to the computer (USB),
    • indication of battery state.

0

3 in stock

Compare

The Sonel MRU-30 uses most known methods of earth resistance measurements. Tests can be performed using the 3-pole, 4-pole, 3-pole with auxiliary clamp and also, additionally, the MRU-30 employs the two clamp method of measurement, without the use of auxiliary test rods which can’t be used in some situations. Complementary features of the MRU-30 are measurements of soil resistivity, continuity measurement of protective and equipotential conductors and, using clamps, leakage currents and interference voltages.

  • Robust and weatherproof (IP65) – no ingress of dust, water protected by a nozzle against enclosure from any direction.
  • Ergonomic casing – small and handy casing to make the measurements more convenient than before.
  • Built-in rechargeable battery – saving time to replace flat batteries; can be recharged from Power Bank and Cigarette Lighter Socket!
  • Clear on-screen notes – displayed on screen before and after the measurement to alert user of possible dangers and irregularities.
  • Many measurement methods available in a small, portable casing
Weight 5 kg
Dimensions 20 × 15 × 7 cm

Measurement of interference voltage UN (RMS)

Range Resolution Accuracy
0…100 V 1 V ±(10% m.v. + 1 digit)

Measurement of continuity of equipotential bondings and protective conductors (Rcont)
measurement range to IEC 61557-4:2007: 0,13 Ω…1999 Ω

Range Resolution Accuracy
0,00…9,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
10,0…99,9 Ω 0,1 Ω
100…1999 Ω 1 Ω

• measurement current: under short circuit >200mA
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)

Measurement of earthing resistance (method 3- and 4-pole)
measurement range to IEC 61557-5:2007: 0,53 Ω…9999 Ω (dla 50 V)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200,0…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• measurement current: under short circuit >20 mA,
• voltage on open terminals: selectable 25 V AC or 50 V AC,
• frequency of measurement current: 125 Hz (for networks 50 Hz) or 150 Hz (for 60 Hz).

Measurement of multiple earthing esistance with using the clamp and auxiliary electrodes (3p + clamp)

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(3% m.v. + 3 digits)
20,0…199,9 Ω 0,1 Ω
200…1999 Ω 1 Ω ±5% m.v.
2000…9999 Ω 1 Ω ±8% m.v.

• voltage on open terminals: selectable 25 V AC or 50 V AC,
• measurement current: under short circuit >20 mA,
• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz (for networks 60 Hz)
Measurement of resistance of auxiliary electrodes RH i RS

Range Resolution Accuracy
0…999 Ω 1 Ω ±(5% m.v.+ 8 digits)
1,00k…9,99 kΩ 0,01 kΩ
10,0k…19,9 kΩ 0,1 kΩ

 

Measurement of multiple earthing resistance with using double clamps

Range Resolution Accuracy
0,00…19,99 Ω 0,01 Ω ±(10% m.v. + 8 digits)
20,0…99,9 Ω 0,1 Ω ±(20% m.v. + 3 digits)

• frequency of measurement current: 125 Hz (for networks 50 Hz) and 150 Hz
(for networks 60 Hz)

Measurement of ground resistivity 
Measurement method: Wenner, ρ=2πLRE

Range Resolution Accuracy
0,00…9,99 Ωm 0,01 Ωm depending on measurement
accuracy RE with 4p method,
but not less than ±1 digit
10,0…99,9 Ωm 0,1 Ωm
100…999 Ωm 1 Ωm
1,00…9,99 kΩm 0,01 kΩm
10,0…99,9 kΩm 0,1 kΩm
100…999 kΩm 1 kΩm

L – distance between probes: 1…50 m.. or 1…150 ft

Electric security:

  • type of insulation: double, according to EN 61010-1 i IEC 61557,
  • measurement category: CAT III 300V wg EN 61010-1,
  • protection class acc. to EN 60529: IP65,

Rated operational conditions:

  • operation temperature: -10…+55°C,
  • storage temperature: -20…+80°C,
  • humidity: 20…90%,

Other technical data:

  • LCD display: segment, backlit,
  • dimensions: 200x150x74 mm.

Brand

SONEL

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “MRU-30 Earth Resistance and Resistivity Meter”

There are no reviews yet.

  • YIHUA 3010D DC Power supply

    0 out of 5
    (0)

    This model has compact design with all metal construction.

    1.This unit now features a Dual LED display with highly accurate LED digital readout.

    2.Maximum output is 30V at 10A.

    1. High stabilized output voltage.
    2. Short circuit protection.

    5.Over loading and current protection.

    SKU: n/a
  • CLAMP METER AC BM 819

    0 out of 5
    (0)
    SKU: n/a
  • JM-6091 37 in 1 Multi-functional Screwdriver Tool Set

    0 out of 5
    (0)

    Features:

    37-in-1 interchangeable precise manual tool set.

    Professional portable hardware tools.
    Light weight, compact design.
    High hardness and good toughness.
    PP&TPR material, non-slip handle.
    Magnetic extension bar, whose lenth can be adjusting on the basis of different applications, is easy for removing and installing.
    It can be used to remove the small part of your cellphone/computer/Mp4…and to repair the device without damaging it.
    SKU: n/a
  • LM40 Laser Distance Meter

    0 out of 5
    (0)

    1. Ergonomic exterior, comfortable handling

    2. Millimeter accuracy
    3. Large, multiple angle HD display
    5. Physical and electronics leveler
    6. Multiple functions: Max/Min/continuous measurement, displacement calculation, data storage, and more
    7. Auto power off after 3 minutes without operation
    SKU: n/a
  • SVC 7000VA

    0 out of 5
    (0)

    Input=120V 270
    Output=220
    Under and Over Volt Protection
    Surge Protection
    Over Load and Heat Protection
    Copper Wind with LCD Display

    SKU: n/a