UT526 is a multifunctional electrical installation tester. It can be used to test insulation resistance, RCD status, low resistance continuity, and voltage measurements. UT526 can be used to test power distribution system, lightning protection system and wiring systems to ensure safe operations.
Specifications of UT526 Multifunction Electrical Meter
Specifications | Range | UT526 | |
Insulation resistance (Ω) | Test voltages | 250V/500V/1000V | ±10% |
250V | 0.05MΩ~200MΩ | ±(5%+5) | |
500V | 0.05MΩ~300MΩ | ±(5%+5) | |
1000V | 0.05MΩ~500MΩ | ±(5%+5) | |
Load current | 250V (R=250kΩ) 1mA | ±10% | |
500V (R=500kΩ) 1mA | ±10% | ||
1000V (R=1MΩ) 1mA | ±10% | ||
Short circuit current | <2mA | √ | |
RCD | Operating voltage (Freq.) | 220V (45Hz~65Hz) | ±10% |
Test current | 10mA/30mA/100mA/300mA | 0~20% | |
Trip time | 0ms~2000ms, 1Δn general (10mA) | ±(5%+2) | |
0ms~500ms, 1Δn general | |||
0ms~300ms, 1Δn general (100mA, 300mA) | |||
Low resistance continuity | Range | 0Ω~2000Ω | ±(2%+5) |
Test voltage | Around 5V | √ | |
Test current | >200mA (R<2Ω) | √ | |
Voltage measurement (V) | DC voltage | 0~440V | ±(5%+2) |
AC voltage | 0~440V | ||
Frequency (For reference only) | √ | ||
Features | |||
Display count | 10000 | ||
Manual range | √ | ||
Phase switch (RCD) | 0°and 180° | √ | |
Low battery indication | √ | ||
Auto AC/DC voltage identification | √ | ||
Red warning lights | √ | ||
General Characteristics | |||
Power | 1.5V battery (LR6) x 6 | ||
Display | 71mm x 34mm | ||
Product color | Red and grey | ||
Product net weight | 380g | ||
Product size | 160mm x 100mm x 71mm | ||
Standard accessories | Batteries, carrying bag, gallus, test leads, alligator clips, test line |
Based on 0 reviews
Be the first to review “UT526 Multifunction Electrical Meter”
-
Clamp Meters
CMP-2000 Digital clamp-on multimeter
It provides:
- AC current measurement (TRUE RMS) up to 1500 A and DC up to 2000 A.
- Measurement of INRUSH current in start-up phase of electrical device.
- AC voltage measurement (TRUE RMS) up to 750 V and DC up to 1000 V.
- Resistance measurement and continuity test:
– continuity test with acoustic signalling (beeper) for resistance below 30 Ω. - Capacitance measurement.
- Temperature measurement (Fahrenheit or Celsius).
- Frequency measurement.
- Duty cycle measurement.
- Diode test.
SKU: n/a -
Earth Ground Resistance Testers
MRU-21 Earth Resistance Meter
Possible measurements:
- earth resistance measurment with 3-pole method,
- measurement of continuity of equipotential bondings and protective conductors with auto-zero function – with current 200 mA,
- resistance measurement using 2-pole method.
SKU: n/a